PDRP-2001 Datasheet, PDF (87/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
Trouble Operation
Operating Instructions
Note: To ensure that the system is functioning properly, the FACP will perform a freeze check five
minutes after the panel is reset, followed by a maintenance check. If there is no freeze or
maintenance condition, the panel will continue to monitor for freeze conditions every hour and
maintenance conditions every four hours.
4.4 Trouble Operation
With no alarms in the system, the detection of a trouble will cause the following:
• The piezo to pulse 1 second On and 1 second Off
• The system Trouble indicator to flash one second On and one second Off
• The output circuits programmed as Trouble Bell NAC to activate
• The trouble relay to activate
• TROUBL with device type, noun/adjective, address and trouble description will appear on
the LCD display
• The same message, along with the time and date, is sent to the optional printer and the history
buffer.
Note that specific troubles will initiate additional actions; for example, loss of AC power will turn
off the AC Power indicator, etc.
Input Zone
For Input Zones, the following is a typical message that could appear on the LCD display for a
device trouble:
TROUBL PULL STATION
<ADJ> <NOUN>
ZONE 1 OPEN FAULT
10:00A 030806
The information displayed in the above example provides the following information:
• First line in display:
 The type of event; in this example OPEN indicating a circuit trouble
 Device type identifier; in this example, PULL STATION indicates a manual device. Other
device type identifiers which can be displayed include 2-WIRE SMOKE for Smoke
Detector, 2-WIRE HEAT for Heat Detector, etc.
• Second line in display:
 <ADJ>; refers to the user programmed adjective descriptor from library list resident in the
control panel or custom entry via PC.
 <NOUN>; refers to the user programmed noun descriptor from library list resident in the
control panel or custom entry via PC.
• Third line in display indicates Zone and the fault condition. Other possible troubles include:
U OPEN - indicating an open circuit
U DIRTY - maintenance alert indicating that a detector is near but below the allowed
alarm limit and is in need of maintenance before the performance is compromised
• Fourth line in display:
 Time; the current time in this example is 10:00A which represents 10:00 AM
 Date; the current month, day and year in this example is 03 for March, 08 for the 8th day
of the month and 06 for the year 2006
PDRP-2001 Series PN 53043:A 5/08/2007
87