PDRP-2001 Datasheet, PDF (42/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel | |||
|
◁ |
Installation
ANN-BUS Devices
2.7.8.1 ANN-LED Board Layout
Figure 2.22 illustrates the ANN-LED board showing locations of screw terminals for
connection to the FACP and the DIP switches for selecting the ANN-BUS ID number.
ANN-BUS (ID#)
Address DIP switch
ANN-BUS Connector
Figure 2.22 ANN-LED Board Layout
2.7.8.2 Specifications
⢠Max. ANN-BUS Voltage: 24 VDC
⢠Max. Current:
Alarm: 68 mA
Standby: 28 mA
⢠Operating Temperature: 32o F to 120o F (0o C to 49o C)
⢠For indoor use in a dry location only
2.7.8.3 Mounting/Installation
Install the ANN-LED Module as described in the documentation supplied with the annunciator.
42