Installation
ANN-BUS Devices
FACP
TB3
4321
ANN-BUS and power wiring are
supervised and power-limited
ANN-80
Figure 2.17 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the FACP.
FACP (TB3)
Terminal 4 GND (-)
Terminal 3 PWR (+)
Terminal 2 A (ANN-BUS)
Terminal 1 B (ANN-BUS)
ANN-80 (TB1)
Terminal 1 (-)
Terminal 2 (+)
Terminal 3 (A)
Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
"ANN-BUS" on page 71 in this manual for detailed programming information. Select the LCD
option for programming.
36
PDRP-2001 Series PN 53043:A 5/08/2007