Programming
Master Programming Level
3.5.7.6 ANN-80 Options
Pressing 2 while ANN-BUS screen #2 will display the following screen:
ANN-80 OPTIONS
1=PIEZO ENABLE
2=LOCK ENABLE
3=ACK BTN ENABLE
ANN-80 Options Screen #1
ANN-80 OPTIONS
1=SIL BTN ENABLE
2=RST BTN ENABLE
3=DRL BTN ENABLE
ANN-80 Options Screen #2
The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 annunciator will ever sound. Pressing 1 while viewing the ANN-80 Options
Screen #1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.
The Lock Enable option allows the programmer to select whether or not the ANN-80 LCD
annunciator must be unlocked by its key before any annunciator key presses will function.
Pressing 2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between
Lock Enable Yes (annunciator must be unlocked for keys to function) and Lock Enable No (lock
position is ignored).
The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 LCD annunciator will function normally
or always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the
display to toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack
Btn Enable No (Ack/Step button never functions).
The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether
the Silence button on any installed ANN-80 LCD annunciator will function normally or always
be ignored. Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to
toggle between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No
(Silence button never functions).
The Reset Button Enable (RST BTN ENABLE) option allows the programmer to select whether
the Reset button on any installed ANN-80 LCD annunciator will function normally or always
be ignored. Pressing 2 while viewing the ANN-80 Options Screen #2 causes the display to
toggle between Rst Btn Enable Yes (Reset button functions normally) and Rst Btn Enable No
(Reset button never functions).
The Drill Button Enable (DRL BTN ENABLE) option allows the programmer to select whether
the Drill button on any installed ANN-80 LCD annunciator will function normally or always be
ignored. Pressing 3 while viewing the ANN-80 Options Screen #2 causes the display to toggle
between Drl Btn Enable Yes (Drill button functions normally) and Drl Btn Enable No (Drill
button never functions).
76
PDRP-2001 Series PN 53043:A 5/08/2007