PDRP-2001 Datasheet, PDF (52/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
Programming
Master Programming Level
Pressing the down arrow key displays additional zone types as indicated in the following table.
Table 3.1 Zone Types
Zone Type
Action When Activated
Pull-Station
Fire Alarm
Manual Release1
Fire Alarm
Normally Open Contact
Fire
N/A
N/A
Waterflow
Fire
Waterflow NS (nonsilenceable)
Fire, nonsilenceable
Combo
Fire/Supervisory
Combo w/AutoResettable Superv2
Fire/Supervisory, nonlatching
2-Wire Smoke
Fire Alarm
2-Wire Heat
Fire Alarm
Linear Heat
Fire Alarm
N/A
N/A
Fire
Fire Alarm
Low Pressure
Supervisory, latching
Low Pressure AutoResettable2
Supervisory, nonlatching
High Pressure
Supervisory
High Pressure AutoResettable2
Supervisory, nonlatching
Disable Release3
Supervisory, nonlatching (disables Release Circuits)
Supervisory
Supervisory, latching
Supervisory AutoResettable2
Supervisory, nonlatching
N/A
2nd-Shot Water Switch4
Fire Alarm, nonlatching
Table Footnote
1. Activation of a Manual Release Switch will override Predischarge Delay,
resulting in an immediate water release.
2. AutoResettable means that a device with this type code, when activated, will
automatically reset when the corresponding condition is cleared.
3. Disable Release allows the installer to disable the releasing solenoids during
system testing. Disable Release will only work when the system is not in alarm.
4. The 2nd-Shot Water Switch provides the option of performing another immediate
water release manually. Refer to "2nd-Shot Water Switch" on page 90.
While viewing any Zone Type screen, select the type of zone being programmed by pressing the
corresponding keyboard number key. The display will return to Edit Input Zone Screen #2 and
indicate the selection next to the Type option.
52
PDRP-2001 Series PN 53043:A 5/08/2007