Template 11: Single Hazard - 3 Zones and Low Pressure
FACP Configuration Templates
B.5 Template 11: Single Hazard - 3 Zones and Low Pressure
TEMPLATE 11: SINGLE HAZARD - 3 ZONES AND LOW PRESSURE
INPUT ZONES
1
2
3
4
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW MANUAL
RELEASE
#1 ALARM NAC
X
X
X
#2 WATERFLOW NAC
X
#3 SUPV. BELL NAC
#4 RELEASE SOLENOID 1
X
X
X
5
PULL
STATION
X
X
6
LOW
PRESS.
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Input Zone Types:
⢠Zone 1 = 2-wire smoke
⢠Zone 2 = Fire
⢠Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
⢠Zone 4 = Manual Release
⢠Zone 5 = Pull Station
⢠Zone 6 = Low Pressure
Output Circuit Types:
⢠Output 1 = Alarm NAC
⢠Output 2 = Waterflow NAC - activation delayed for 10 secs. (Waterflow Delay set to10 secs.)
⢠Output 3 = Supervisory Bell NAC
⢠Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
⢠Soak Timer 1 - set for 10 minutes
⢠Soak Timer 2 - set for 10 minutes
⢠Waterflow Delay Timer - set for 10 seconds
⢠AC Loss Delay Timer - set for 2 hours
Operation
⢠Activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 4 (Manual Release) or
Zone 5 (Pull Station) will operate the Alarm NAC Output #1 and Release Solenoid 1 Output
#4. Release Solenoid 1 will turn off water release following time-out of the 10 minute Soak
Timer 1
⢠Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
⢠Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
⢠Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
⢠Trouble Relay - any system trouble will activate the Trouble Relay
⢠Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay