English
Language : 

PDRP-2001 Datasheet, PDF (114/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
FACP Configuration Templates
Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active
B.6 Template 12: Single Hazard - 2 Zones Cross-Zoned With All Active
TEMPLATE 12: SINGLE HAZARD - 2 ZONES CROSS-ZONES WITH ALL ACTIVE
INPUT ZONES
1
2
3
4
5
OUTPUT CIRCUITS
2-WIRE SMOKE
FIRE
WATERFLOW MANUAL
PULL
RELEASE STATION
#1 ALARM NAC
X
X
X
X
#2 WATERFLOW NAC
X
#3 SUPV. BELL NAC
#4 RELEASE SOLENOID 1
C1
C1
X
X
6
LOW
PRESS.
X
Table Legend:
X = direct correlation between Input Zone and Output Circuit (input zone activation will turn on corresponding
output circuit).
Cx = cross-zone where x is the number of the Release Solenoid. All inputs with the same Release Solenoid
number must be active at the same time to turn on the corresponding solenoid output circuit
Input Zone Types:
• Zone 1 = 2-wire smoke
• Zone 2 = Fire
• Zone 3 = Waterflow - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
• Zone 4 = Manual Release
• Zone 5 = Pull Station
• Zone 6 = Low Pressure
Output Circuit Types:
• Output 1 = Alarm NAC
• Output 2 = Waterflow NAC - activation delayed for 10 seconds (Waterflow Delay set to 10 secs.)
• Output 3 = Supervisory Bell NAC
• Output 4 = Release Solenoid 1 (unsupervised for shorts)
Timers
• Soak Timer 1 - set for 10 minutes
• Soak Timer 2 - set for 10 minutes
• Waterflow Delay Timer - set for 10 seconds
• AC Loss Delay Timer - set for 2 hours
Operation
• Activation of both Input Zone 1 (2-Wire Smoke) and Zone 2 (Fire) at the same time, or Zone
4 (Manual Release) or Zone 5 (Pull Station) will operate the Release Solenoid 1 Output #4.
Release Solenoid will turn off water release following time-out of the 10 minute Soak Timer
1. Activation of any one of these zones will operate Alarm NAC Output #1
• Activation of Input Zone 3 (Waterflow) will operate the Waterflow NAC Output #2. There is
a 10 second FACP initiated delay in activation since Waterflow Delay Timer is set to 10
seconds
• Activation of Input Zone 6 (Low Pressure) will operate the Supervisory Bell NAC Output #3
FACP Relay Operation
The following description of FACP relay operations are in addition to normal system operation.
• Alarm Relay - activation of Input Zone 1 (2-Wire Smoke) or Zone 2 (Fire) or Zone 3
(Waterflow - with Waterflow Delay time) or Zone 4 (Manual Release) or Zone 5 (Pull
Station) will operate Alarm Relay
• Trouble Relay - any system trouble will activate the Trouble Relay
• Supervisory - activation of Zone 6 (Supervisory) will operate the Supervisory Relay
114
PDRP-2001 Series PN 53043:A 5/08/2007