PDRP-2001 Datasheet, PDF (33/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
ANN-BUS Devices
Installation
2.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 2.16 illustrates the powering of ANN-BUS devices from an auxiliary power supply such
as the FCPS-24S6/8, when the maximum number of ANN-BUS devices exceeds the ANN-BUS
power requirements.
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
TB3
FACP
ANN-BUS
-24 VDC
+24 VDC
ANN-80
ANN-BUS and power wiring are
supervised and power-limited
FCPS-24S6/8
Figure 2.16 Powering ANN-BUS Devices from FCPS-24S6/8
2.7.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled "ANN-BUS" on page 71).
A maximum of 8 devices can be connected to the FACP ANN-BUS communication circuit. Device
addresses do not need to be sequential and can be set to any number between 01 and 08. Note that
00 is not a valid address. The following table shows the DIP switch setting for each address.
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions.
Unless otherwise specified in the documentation supplied with each device, switch positions 6 and
above must be set to OFF.
Address
not valid
01
02
03
04
05
06
07
08
Switch 5
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Switch 4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
Switch 3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
Switch 2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
Switch 1
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
PDRP-2001 Series PN 53043:A 5/08/2007
33