PDRP-2001 Datasheet, PDF (21/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
Input Circuits
Installation
2.3 Input Circuits
The PDRP-2001 has six programmable IDCs (Initiating Device Circuits). Each circuit is
compatible with System Sensor’s i3 smoke detectors which generate a maintenance signal when the
detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls
below the detector rating of approximately 45oF. The maximum loop resistance limit for each IDC
is 100 ohms. The maximum number of detectors per zone is 25. The field wiring for each zone is
supervised for opens, shorts and ground faults. All conditions are visually and audibly
annunciated.
Each circuit is configured for Style B (Class B) operation and will accept i3 smoke detectors, any
normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.
Refer to the Device Compatibility Appendix for a list of compatible devices.
Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A
Converter module. Refer to "CAC-5X Class A Converter Module" on page 26.
Class B Initiating Device Circuits (supervised and power-limited) 4.7 KΩ, ½ watt resistor P/N:71252
UL listed Power Supervision Relay
(refer to Device Compatibility Appendix for list of compatible relays)
UL listed compatible 4-wire smoke detector
Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)
manual pull stations
heat detectors
Dummy load all unused
circuits - 4.7 KΩ, ½ watt
resistor (P/N: 71245)
manual
release
Input IDC
Waterflow Circuit
Normally Open
Waterflow
Devices or
Pressure Switches
Figure 2.5 IDC Connections
PDRP-2001 Series PN 53043:A 5/08/2007