PDRP-2001 Datasheet, PDF (120/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
NFPA Standard-Specific Requirements
NFPA 72 Auxiliary Fire Alarm System
NFPA 72 Remote Station Protective Signaling System
Notes:
1. Cut Jumper JP30 on the PDRP-2001/E main circuit board to supervise placement of the
4XTM module.
2. Refer to "4XTM Transmitter Module Installation" on page 29 for detailed information.
RS82 Remote Station Receiver UL listed.
Refer to Instruction Manual for Remote Station Receiver
Model RS82.
Polarity Shown is
+ - Normal Standby
Cutting TBL Jumper allows the
reverse polarity circuit to open
with a system trouble condition
if no alarm condition exists.
+
Power-limited
-
(Dummy load with a 4.7KΩ, ¼ watt
resistor when no connection is made)
4XTM Transmitter Module
Figure C.3 Remote Station Connection Using 4XTM Module
120
PDRP-2001 Series PN 53043:A 5/08/2007