Circuit Mapping and Cross-Zoning
Input-to-Output Circuit Mapping and Cross-Zone Operation
Example 4: A dual hazard, cross-zoned application using four input zones and two releasing output
circuits. Input Zones 1 and 2 are cross-zoned to activate Output Circuit 2, which is programmed as
RELEASE 1. Input Zones 3 and 4 are cross-zoned to activate Output Circuit 3, which is
programmed as a RELEASE 2.
• Output Circuit 1 is programmed as alarm NAC using the OUTPUT CIRCUITS menus.
• Output Circuit 2 is programmed as Release Circuit 1 using the OUTPUT CIRCUITS menus.
• Output Circuit 3 is programmed as Release Circuit 2 using the OUTPUT CIRCUITS menus
• Output Circuit 4 is programmed as supervisory NAC using the OUTPUT CIRCUITS menus.
• Any of smoke detector Input Zones 1 through 4 will directly activate Output Circuit 1 (Alarm
NAC) but not Output Circuits 2, 3 or 4.
• Smoke detector Input Zones 1 and 2 are cross-zoned (both must be in alarm) to activate
Output Circuit 2 (Release 1) but not Output Circuits 3 or 4.
• Smoke detector Input Zones 3 and 4 are cross-zoned (both must be in alarm) to activate
Output Circuit 3 (Release 2) but not Output Circuits 2 or 4.
ZONE 1 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
ZONE 3 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
ZONE 2 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
ZONE 4 TYPE
1=COMBO
2=COMBO W/AR. SUPERV
3=2-WIRE SMOKE
OUTPUT MAP ZONE 1
1=ALARM NAC
YES
2=RELEASE 1
YES
3=RELEASE 2
NO
OUTPUT MAP ZONE 2
1=ALARM NAC
YES
2=RELEASE 1
YES
3=RELEASE 2
NO
OUTPUT MAP ZONE 1
1=SUPV BELL NAC
N/A
OUTPUT MAP ZONE 2
1=SUPV BELL NAC
N/A
OUTPUT MAP ZONE 3
1=ALARM NAC
YES
2=RELEASE 1
NO
3=RELEASE 2
YES
OUTPUT MAP ZONE 3
1=SUPV BELL NAC
N/A
OUTPUT MAP ZONE 4
1=ALARM NAC
YES
2=RELEASE 1
NO
3=RELEASE 2
YES
OUTPUT MAP ZONE 4
1=SUPV BELL NAC
N/A
REL 1 CROSS GROUP 1
1=ZONE 1
YES
2=ZONE 2
YES
3=ZONE 3
NO
REL 2 CROSS GROUP 1
1=ZONE 1
NO
2=ZONE 2
NO
3=ZONE 3
YES
REL 2 CROSS GROUP 1
1=ZONE 4
YES
2=ZONE 5
NO
3=ZONE 6
NO
106
PDRP-2001 Series PN 53043:A 5/08/2007