PDRP-2001 Datasheet, PDF (119/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
NFPA 72 Auxiliary Fire Alarm System
NFPA Standard-Specific Requirements
C.1 NFPA 72 Auxiliary Fire Alarm System
All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.
Notes:
1. 3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.
2. Cut JP30 on the PDRP-2001/E main circuit board to supervise placement of 4XTM module
and circuit.
3. Cut JP24 on the PDRP-2001/E main circuit board to enable FACP Supervisory relay.
4. Refer to "4XTM Municipal Box Transmitter Option Module" on page 28 for detailed
information.
Figure C.2 Municipal Box Connected to 4XTM Transmitter Module
+
Municipal Box
Circuit -
FIRE
Gamewell Model M34-56
Local Energy Municipal Box
Polarities shown in alarm condition
+
Nonpower-limited
-
4XTM
Figure A.2 Municipal Box Connected to 4XTM Transmitter Module
PDRP-2001 Series PN 53043:A 5/08/2007
119