PDRP-2001 Datasheet, PDF (57/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
Master Programming Level
Programming
3.5.3 Output Circuits
The options for the Output Circuits on the control panel main circuit board can be configured by
pressing 2 while viewing Programming Screen #2. The following screens will be displayed:
PROGRAMMING
1=FACP CONFIG
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
OUTPUT CIRCUITS
1=OUTPUT 1
2=OUTPUT 2
3=OUTPUT 3
NAC Selection Screen
OUTPUT CIRCUITS
1=OUTPUT 4
NAC Selection Screen
The Output Circuits can be configured independently by pressing 1 for Output 1, 2 for Output 2, 3
for Output 3 or 4 for Output 4.
To program an Output circuit, press the number corresponding to the Output to be programmed.
The following screens will be displayed for each selection:
OUTPUT #
1=ENABLED
YES
2=TYPE
ALARM NAC
Output Screen #1
OUTPUT #
1=SILENCE
NON-SIL
2=AUTO SILENCE
NO
3=SIL INHIBIT
NO
Output Screen #2
OUTPUT #
1=CODING
STEADY
Output Screen #3
PDRP-2001 Series PN 53043:A 5/08/2007
57