PDRP-2001 Datasheet, PDF (77/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
Master Programming Level
Programming
PROGRAMMING
1=ANN-RLY OPTIONS
2=ANN-LED OPTIONS
ANN-BUS Screen #3
3.5.7.7 ANN-RLY Options
Pressing 1 for ANN-RLY Options while viewing ANN-BUS Screen #3 will cause the following
screen to be displayed:
ANN-RLY OPTIONS
1=RELAY 1 IN ZONE 1
2=RELAY 2 IN ZONE 2
3=RELAY 3 IN ZONE 3
ANN-RLY Options Screen
The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option
screen, press the number key corresponding to the relay to be programmed. Following is a list
of the available programming options for each relay:
• General Alarm
• General Trouble
• General Supervisory
• Future Use
• Future Use
• Future Use
• General Discharge
• Discharge Release 1
• Discharge Release 2
• AC Loss
• Waterflow Delay
• Future Use
• Future Use
• Future Use
• General 2nd Shot Release
• 2nd Shot Release 1
• 2nd Shot Release 2
• Input Zone 1
• Input Zone 2
• Input Zone 3
• Input Zone 4
• Input Zone 5
• Input Zone 6
PDRP-2001 Series PN 53043:A 5/08/2007