PDRP-2001 Datasheet, PDF (49/140 Pages) Systemsensor advanced ideas. – Deluge Preaction Control Panel
Master Programming Level
Programming
3.5 Master Programming Level
When the Master Program Level password is entered, the control panel will enter user
Programming mode. In this mode, the piezo sounder remains off, the trouble relay is activated and
the system Trouble indicator flashes until Programming mode is exited. The following display will
appear:
PROGRAMMING
1=FACP CONFIG
T7
2=INPUT ZONES
3=OUTPUT CIRCUITS
Programming Screen #1
The down arrow which appears in the display indicates that additional programming choices can be
viewed by pressing the down arrow key on the keypad. If a down and up arrow appear in the
display, pressing the ‘down’ arrow key will display the subsequent Programming Screens as
illustrated below while pressing the ‘up’ arrow key will display the previous screen.
PROGRAMMING
1=CROSS INPUT ZONES
2=ON-BOARD RELAYS
3=SYSTEM SETUP
Programming Screen #2
PROGRAMMING
1=ANN-BUS
2=HISTORY 256 EVENTS
3=WALKTEST
Programming Screen #3
PROGRAMMING
1=CLEAR PROGRAM
2=PASSWORD CHANGE
Programming Screen #4
PDRP-2001 Series PN 53043:A 5/08/2007