3UG4622-1AW30 Datasheet, PDF (98/114 Pages) List of Unclassifed Manufacturers – Monitoring and Control Devices
Monitoring Relays
3RN1 Thermistor Motor Protection
For PTC sensors
3RN10 62 tripping units for multiple motor protection
Up to 6 sensor circuits can be connected to the 3RN10 62
tripping unit, all of which act on one output relay. The
simultaneous protection of several motors (up to 6) is an
advantage for multi-motor drives (e.g. if one motor is
overloaded, all the other motors of the drive will be shut down).
Apart from the red LED TRIPPED, which signals the switching
status of the tripping unit, an LED is assigned to each sensor
circuit which indicates the sensor circuit that has responded.
Unused sensor circuits must be short-circuited.
The reset response of the 3RN10 62 tripping units can be
changed from manual RESET to automatic RESET by linking
terminals Y1 and Y2. Remote RESET is implemented by
connecting an external pushbutton with a normally-open
function.
Response of the tripping units in the event of control voltage
failure
Behavior
for
Monostable
3RN10 00
3RN10 10
3RN10 11
Failure of the
Device trips
control voltage
Return of the
Device resets
control voltage
without a
preceding
tripping operation
Return of the
Device resets
control voltage
after a preceding
tripping operation
Non-volatile
Monostable
3RN10 12
3RN10 13-...0
3RN10 22
3RN10 62
Device trips
Device resets
Bistable
3RN10 13-...01
No change in
state of the
auxiliary contacts
No change in
state of the
auxiliary contacts
The device
remains tripped
No change in
state of the
auxiliary contacts
3RN10 111)
A 1 /A 2
3800
1500
T 1 /T 2
(Y 1 /Y 2 )
K
L E D T r ip p e d
N S B 0_00315c
3RN10 13-...01
A1/A2
3800
1500
T1/T2
RESET
(Y1/Y2)
K
LED Tripped
NSB0_00316a
3RN10 121)/3RN10 22/3RN10 62
A1/A2
3800
1500
T1/T2
RESET
(Y1/Y2)
NSB0_00317a
K, K2
LED Tripped
Safe electrical isolation
All circuits (outputs, control circuits, sensor and RESET circuits)
of the multifunction tripping units 3RN10 13-1BW10 and
3RN10 13-1GW10 (wide voltage range, monostable output relay
and screw-type terminals) are safely isolated from each other
up to a rated voltage of 300 V according to DIN VDE 0100
Part 410/EN 60947-1.
Function diagrams
3RN10 00/3RN10 10
(Auto-RESET)
A1/A2
3800
1500
T1/T2
K
LED Tripped
NSB0_00314b
3RN10 13-...0
A1/A2
3800
1500
T1/T2
RESET
(Y1/Y2)
K
LED Tripped
3RN10 22 only
3800
1500
2T1/T2
K1
LED Alarm
NSB0_00319b
NSB0_00318a
1) For versions with 2 CO (3RN10 1.G...): See 3RN10 13. function diagram
for short-circuit response of sensor circuit.
7/98
Siemens LV 1 T · 2006