English
Language : 

3UG4622-1AW30 Datasheet, PDF (79/114 Pages) List of Unclassifed Manufacturers – Monitoring and Control Devices
Monitoring Relays
3UG Monitoring Relays for Electrical and Additional Measurements
Insulation monitoring
for ungrounded AC networks
■ Technical specifications
Control circuits
Operating range of the control supply voltage
Rated power
24 ... 240 V AC/DC
110 ... 130 V AC
220 ... 240 V AC
Frequency of the rated control supply voltage
Measurement circuits L/PE/ground
• Operating value
• Minimum internal resistance for AC
• Minimum internal resistance for DC
• DC measurement voltage
• Insulation voltage
• Reset/test function terminals (max. 10 m)
• Delay time in case of response
Output relay
General data
Rated insulation voltage Ui
Overvoltage category
Degree of pollution
Impulse withstand voltage Uimp
Degree of protection
Shock resistance
Vibration resistance
Permissible ambient temperature
• During operation
• During storage
Permissible mounting position
Conductor cross-section
between supply, measurement,
and output circuit
acc. to IEC 664
acc. to IEC 664
acc. to VDE 0435, Part 303
acc. to EN 60529
acc. to IEC 60068 Part 2-27
acc. to IEC 60068-2-6
Solid
Finely stranded with end sleeve
3UG3 081
VA/W
VA
VA
Hz
-15 % ... +10 %
8/2
3
3
50 ... 60
k
1 ... 110
k
100
k
100
V
30 DC
V
415 AC
Y1-Y2
s
1
1 CO contact,
open-circuit principle
V
400 acc. to IEC 60947-1
III
3
kV 4
IP50 enclosure, IP20 terminals
g/ms 10
Hz/mm 10-55/0.35
°C
°C
mm2
mm2
-25 ... 65
-40 ... 85
Any
2 x 0.75 ... 2.5
2 x 0.75 ... 2.5
■ Dimensional drawings
45
77
100
Siemens LV 1 T · 2006
7/79