3UG4622-1AW30 Datasheet, PDF (35/114 Pages) List of Unclassifed Manufacturers – Monitoring and Control Devices
SIMOCODE 3UF Motor Management and Control Devices
3UF18 current transformers
for overload protection
■ Overview
The 3UF1 8 current transformers are protection transformers and
are used for actuating overload relays. Protection transformers
are designed to ensure proportional current transfer up to a
multiple of the primary rated current. The 3UF18 current
transformers convert the maximum current of the corresponding
operating range into the standard signal 1 A secondary.
■ Technical specifications
Climatic environmental conditions
Temperatures
• Operation
°C
• Storage/transport
°C
Temperature changes
• Operation
°C/h
• Storage/transport
°C/h
Relative humidity
%
Air pressure
• Operation
hPa
• Storage/transport
hPa
Contaminants
• SO2
• H2S
ppm
ppm
Mechanical environmental conditions
Vibrations
Hz
(acc. to IEC 60068-2-6)
Hz
Shock (acc. to IEC 60068-2-27)
Requirements acc. to IEC and DIN
Degree of protection (acc. to IEC 60529)
Rated insulation voltage
V
Rating of the insulation
V
(acc. to UL/CSA)
Trip class (acc. to IEC 60947-4-1)
Power loss per conducting path of the
transformers
• 3UF18 45
• 3UF18 48
• 3UF18 50
• 3UF18 52
• 3UF18 56
• 3UF18 57
• 3UF18 68-3F
• 3UF18 68-3G
Conductor cross-sections
(one or two conductors connectable)
• Terminal screw
• Solid
• Stranded
• Finely stranded without end sleeve
• Finely stranded with end sleeve
• Finely stranded with cable lug
• Stranded with cable lug
• Connecting bars
• Tightening torque
• Tightening torque
mm2
mm2
mm2
mm2
mm2
mm2
mm
Nm
lb
-25 ... +60
-40 ... +85
max. 10
max. 20
15 ... 95 (indoor, acc. to IEC 60721-3, no condensation)
860 ... 1060
650 ... 1060
0.5 (relative humidity ˆ 60 %, no condensation)
0.1 (relative humidity ˆ 60 %, no condensation)
10 ... 57 (for constant amplitude 0.15 nm)
57 ... 150 (for constant acceleration 2 g)
12 shocks (half sine 15 g/11 ms)
IP20
690/1000 (type-dependent)
600
Suitable from CLASS 5 to CLASS 30
Operating range
for setting ...
to the lower limit
to the upper limit
A
12.5 ... 50
25 ... 100
32 ... 130
50 ... 200
100 ... 400
125 ... 500
160 ... 630
205 ... 820
mW (mVA)
33 (38)
110 (120)
135 (150)
170 (190)
450 (500)
850 (940)
900 (1000)
1400 (1600)
mW (mVA)
570 (650)
1700 (1900)
2400 (2700)
2600 (2900)
6500 (7000)
13000 (15000)
17000 (19000)
22000 (25000)
Current transformers
on second- on primary side
ary side
3UF18 45 3UF18 481) 3UF18 501) 3UF18 52 3UF18 56
3UF18 572)
M 3.5
for connec- for connec- for connec- M 8
2 ™ 1.5 ... 2.5 tion data tion data tion data --
2 ™ 1.5 ... 2.5
see 3RT
Contactors
see 3RT
Contactors
see 3RT
Contactors
--
--
--
M 10
--
--
--
2 ™ 1.5
--
--
--
--
35 ... 95
50 ... 120
20 ™ 4
--
50 ... 2403)
70 ... 2403)
25 ™ 6.30 ™
6
0.8 ... 1.4
10 ... 14 14 ... 24
7 ... 12
89 ... 124 124 ... 210
3UF18 68-
3FA002)
M 10
--
--
--
--
50 ... 240
70 ... 240
30 ™ 5
14 ... 24
124 ... 210
3UF18 68-
3GA002)
M 12
--
--
--
--
185 ... 240
185 ... 240
50 ™ 5
14 ... 24
124 ... 210
1) With or without box terminal.
2) Conductor cross-sections for box terminals, see 3TF6 8 and 3TF6 9
contactors in the section Contactors and Contactor Assemblies.
3) With max. conductor cross-section, a terminal cover for maintaining the
phase spacing is required.
Siemens LV 1 T · 2006
7/35