English
Language : 

3UG4622-1AW30 Datasheet, PDF (32/114 Pages) List of Unclassifed Manufacturers – Monitoring and Control Devices
SIMOCODE 3UF Motor Management and Control Devices
SIMOCODE-DP 3UF5
motor protection and control devices
Short-circuit protection with fuses for motor feeders
with short-circuit currents up to 50 kA at 690 V for 3RB1 2 and 3UF5 0, Part 2
Basic units
Contactors
Setting range 1.25 ... 6.3 A
3UF5 00
3RT1 015
3RT1 016
3RT1 017
Setting range 6.3 ... 25 A
3UF5 01
3RT1 015
3RT1 016
3RT1 017
3RT1 024
3RT1 025
3RT1 026
3RT1 034
3RT1 035
Setting range 25 ... 100 A
3UF5 02
3RT1 034
3RT1 035
3RT1 036
3RT1 044
3RT1 045
3RT1 046
Setting range 50 ... 205 A
3UF5 03
3RT1 054
3RT1 055
3RT1 056
Setting range 125 ... 500 A
3UF5 04
3RT1 064
3RT1 065
3RT1 066
3RT1 075
3RT1 076
3RT1 264
3RT1 265
3RT1 266
3RT1 275
3RT1 276
Setting range 200 ... 820 A
3UF5 05
3TF6 83)
3TF6 93)
Fuse links1)
690 V
LV HRC
DIAZED
NEOZED
Operational class gL
(gG)
Type of coordination2)
1
Type 3NA
Type 5SB
Type 5SE
2
35
20
35
20
35
20
35
20
35
20
35
20
63
25
63
25
100
35
125
63
125
63
125
63
125
63
160
80
250
125
250
160
250
160
355
315
355
315
355
315
500
500
500
630
630
500
500
500
800
800
1000
1250
400
400
400
400
500
500
500
500
800
800
5004)
6304)
Type 3ND
aM
20
20
20
50
50
50
50
50
63
80
100
160
200
200
250
315
315
400
500
400
400
400
630
630
630
630
1) Note the operational voltage.
2) Assignment and short-circuit protective devices
acc. to IEC 60947-4-1:
Type of coordination "1": Contactors or starters must not endanger
persons or equipment in the event of a short-circuit. They do not have to
be suitable for further operation without repair and the renewal of parts.
Type of coordination "2": Contactors or starters must not endanger
persons or equipment in the event of a short-circuit and must be suitable
for continued use. There is a risk of contact welding.
3) Contactors mountable.
4) Ensure that the maximum AC-3 operational current is sufficiently different
from the rated fuse current.
415 V
600 V
British Standards UL-listed fuses RK5/L
fuses BS88
500
20
25
20
25
20
25
20
60
20
60
20
60
25
70
25
70
25
100
63
100
63
100
63
125
80
150
80
200
125
250
160
250
160
350
250
450
315
500
315
500
400
700
400
800
400
800
450
1000
500
1200
450
800
450
800
450
800
800
1200
800
1200
500
1200
630
2000 CLASS L
7/32
Siemens LV 1 T · 2006