English
Language : 

3UG4622-1AW30 Datasheet, PDF (102/114 Pages) List of Unclassifed Manufacturers – Monitoring and Control Devices
3TK28 Safety Relays
With electronic enabling circuits
■ Overview
The SIRIUS safety pilot guides you quickly to the right device
Type
Connection
1-channel
3TK28 40
✔
basic unit
3TK28 41
✔
standard unit
3TK28 42
✔
standard unit
tv
3TK28 45
✔
multi-function
unit
2-channel
✔
✔
✔
✔
Crossover
protection
✔
✔
✔
✔
Category acc. to EN 954-1
B1234
✔ ✔ ✔ ✔ --
EMERGENCY- Protective
STOP
door
✔
✔
✔✔✔✔✔
✔
✔
✔✔✔✔✔
✔
✔
✔✔✔✔✔
✔
✔
Solid-state
sensors
--
Cascading
input
24 V DC
--
Safety mats
--
✔
1
✔
✔
1
✔
✔
1
✔
Type
Enabling circuit,
floating
Enabling circuit,
solid-state
Signal-
ing
circuit
Stop Stop Stop Stop
category category category category
0
1
0
1
3TK28 40
--
--
21)
--
--
basic unit
3TK28 41
--
--
2
--
--
standard unit
3TK28 42
--
--
1
1
--
standard unit
tv
3TK28 45
1
1
1
1
1 HL
multi-function
unit
2
--
2
--
1 HL
✔ = available
-- = not available
Autostart Moni-
tored
start
✔
✔
Switching capacity Rated operational Rated control supply Control
voltage
voltage
inputs
AC-15 DC-13
at
at
U=230 V U=24 V
--
0.5 A
24 V
DC
✔
230 V 600 V 24 V
AC AC DC
--
--
✔
115 V 230 V 24 V
AC AC DC
-- --
--
✔
✔
--
1.5 A ✔
--
--
✔
--
--
--
✔
✔
--
1.5 A ✔
--
--
✔
--
--
--
✔
✔
2A
1.5 A ✔
✔
--
✔
--
--
--
1) The outputs are only safe when an external contactor is used.
■ Design
The solid-state safety relays can be used in EMERGENCY-STOP
devices to EN 418 and in safety circuits to EN 60204-1 (11.98),
for example, for moving covers and protective doors.
Depending on the device type and the external circuit, the
maximum category that can be achieved is Category 4 of
EN 954-1 or SIL 3 according to IEC 61508.
Installation
For snap-on mounting on 35 mm standard mounting rail
according to EN 50022. Screw fixing is also possible for the
devices by means of 2 additional 3RP19 03 push-in lugs.
■ Function
The electronics (based on the example of a 3TK28 41)
7 The internal circuit is configured with redundancy and
diversity. The processors monitor each other dynamically.
7 The output drivers are also redundant and diverse. They are
monitored by a cyclic self-test.
7 All sensor signals are dynamically tested. This enables faults
to be detected on the sensors, wires (cross-circuit) etc.
7 The field-effect transistor (FET) is switched by both
processors. The output driver must be activated
simultaneously by one of the two processors. Only then is the
voltage connected safely from power supply terminal A1 to
output terminals 14 + 24.
7 All solid-state switches (FET + output driver) are dynamically
monitored by the processors.
7 The required functionality (1-channel or 2-channel), monitored
start or autostart, EMERGENCY-STOP, protective door and
cascading is set by means of jumpers at the connection
terminals.
Y11 Y12 Y35 Y21 Y22 Y32 Y34 1
A1
FET
µC1
µC2
AusOguatnpgust tdreriivbeerr
A2
14 24
7/102 Siemens LV 1 T · 2006