English
Language : 

3UG4622-1AW30 Datasheet, PDF (6/114 Pages) List of Unclassifed Manufacturers – Monitoring and Control Devices
SIMOCODE 3UF Motor Management and Control Devices
SIMOCODE pro 3UF7
motor management and control devices
SIMOCODE pro C, basic unit 1
The compact system for
• Direct-on-line and reversing starters
• Actuation of a circuit-breaker (MCCB)
with up to 4 binary inputs, up to 3 monostable relay outputs and
one thermistor connection (binary PTC)
The basic unit 1 is available in two different variants for the
following supply voltages:
• 24 V DC
• 110 ... 240 V AC/DC
SIMOCODE pro V, basic unit 2
The variable system which offers all SIMOCODE pro C functions
plus many additional functions. Basic unit 2 supports the
following control functions:
• Direct-on-line and reversing starters
• Star/delta starters, also with direction reversal
• Two speeds, motors with separate windings (pole-changing
switch); also with direction reversal
• Two speeds, motors with separate Dahlander windings (also
with direction reversal)
• Slide control
• Solenoid valve actuation
• Actuation of a circuit-breaker (MCCB)
• Soft starter actuation (also with direction reversal)
Basic unit 2 has 4 binary inputs, 3 monostable relay outputs and
one thermistor connection (binary PTC). The type and number of
inputs and outputs can be increased by means of additional
expansion modules.
Basic unit 2 is available in two different variants for the following
supply voltages:
• 24 V DC
• 110 ... 240 V AC/DC
SIMOCODE pro C, basic unit 1
Inputs:
• 4 binary inputs, with internal supply from 24 V DC
Outputs:
• 3 (2+1) monostable relay outputs
Thermistor connection for binary PTC
PROFIBUS interface:
• 9-pole SUB-D or
• Terminal connection
Connection of the supply voltage:
• 24 V DC or
• 110 ... 240 V AC/DC
Test/Reset button
3 LEDs
2 system interfaces for connection of
• a current measuring module and
• an operator panel
Basic unit 1 is suitable for standard rail mounting or, with
additional push-in lugs, for fixing to a mounting plate.
SIMOCODE pro V, basic unit 2
Inputs:
• 4 binary inputs, with internal supply from 24 V DC
Outputs:
• 3 (2+1) monostable relay outputs
Thermistor connection for binary PTC
PROFIBUS interface:
• 9-pole SUB-D or
• Terminal connection
Connection of the supply voltage:
• 24 V DC or
• 110 ... 240 V AC/DC
Test/Reset button
3 LEDs
7/6
Siemens LV 1 T · 2006