English
Language : 

3UG4622-1AW30 Datasheet, PDF (113/114 Pages) List of Unclassifed Manufacturers – Monitoring and Control Devices
Interface Converters
■ Technical specifications
3RS17 interface converters
Type 3RS17
24 V AC/DC
24 ... 240 V AC/DC
General data
Supply voltage operating range DC
AC
Rated power
0.7 ... 1.25 x Un
0.8 ... 1.2 x Un
W
Typical 0.3
0.7 ... 1.1 x Un
0.8 ... 1.1 x Un
Typical 0.75
Electrical isolation of input/output
Active disconnector: 1500 V, 50 Hz, 1 min; 4000 V, 50 Hz, 1 min
Passive disconnector: 500 V, 50 Hz, 1 min
Rated insulation voltage Ui pollution degree 2
V
50
300
Overvoltage category III acc. to DIN VDE 0100
Ambient temperature
During operation
During storage
°C -25 ... +60
°C -40 ... +85
Conductor cross-sections
Screw terminals
• Conductor cross-section
- Solid
- Finely stranded with or without end sleeve
• Terminal screw
mm2
mm2
1 x (0.25 ... 4)
1 x (0.5 ... 2.5)
M3
Spring-loaded terminal
• Solid or finely stranded
• Finely stranded with end sleeve
mm2 1 x (0.08 ... 2.5)
mm2 1 x (0.25 ... 1.5)
Degree of protection
Enclosures IEC 529
Terminals IEC 529
IP30
IP20
Permissible mounting position
Any
Mounting onto standard rail EN 50022
mm 35
Vibration resistance IEC 68-2-6
Hz/mm 10-55/0.35
Shock resistance IEC 68-2-27
g/ms 15/11
Input
Impedance
Voltage inputs
Current inputs, active
kW 330
W
100
Input voltage max.
Voltage inputs
Current inputs, active
V
30 AC/DC
V
30 AC/DC
Response current
Current inputs, passive
µA 100/250 (6.2 mm width)
Voltage drop
Current inputs, passive
V
2.7 at 20 mA
Output
Impedance
Voltage output, 0 ... 10 V
W
55
Output load
Current 0/4 ... 20 mA active, max. W
Current 0 ... 20 mA passive, max. W
Frequency, min.
W
400
1000 at 20 mA, 400 at 20 mA (6.2 mm width)
2.400
Output voltage
Frequency
V
20.9
Output current
for supply voltage
Voltage output 0 ... 10 V, max.
Frequency, max.
mA 21
mA 10
Short-circuit current
Voltage output, 0 ... 10 V
mA
Current output, 0 ... 20 mA, passive mA
Frequency
mA
40
Corresponds to the input current
15
Protection of the outputs
Short-circuit resistant
Max. overvoltage at output
V
30
Accuracy
Total error at 23 °C
Active disconnector (frequency)
%
0.1
Active disconnector (U, I)
%
0.11)
Linearity error
Active disconnector (U, I)
Active disconnector (frequency)
%
0.02
%
0.02
Deviation due to ambient
temperature
Active disconnector (frequency)
Active disconnector (U, I)
Passive disconnector
0 ... 50 Hz: 7.5 mHz/K; 0 ... 100 Hz: 15 mHz/K; 0 ... 1 kHz: 0.15 Hz/K;
0 ... 10 kHz: 1.5 Hz/K
0 ... 10 V: 1.5 mV/K; 0/4 ... 20 mA: 3 µA/K
Width 6.2 mm: 100 ppm/K of measured value
Width 12.5 mm: with load < 600 W: < 50 ppm/K of measured value;
with load ˜ 600 W: < 175 ppm/K of measured value
Transmission error
Passive disconnector
%
0.1
Measured value load error
%/W 0.06/100
Limit frequency at 3 dB
Active disconnector (frequency)
Active disconnector (U, I)
Passive disconnector
Hz 30
Hz 30
Hz 50
Rise time (10 to 90 %)
Active disconnector (frequency)
Active disconnector (U, I)
10 + 1 period
ms 10
Settling time
at 1 % accuracy
Active disconnector (frequency)
Active disconnector (U, I)
30 + 1 period
ms 30
Residual ripple
Active disconnector (U, I)
Passive disconnector
mVeff < 5
mVeff < 8
The accuracy refers to the measurement range end value if not otherwise stated.
1) For 3RS17 06: 0.1 % for selected output 4 ... 20 mA; 0.3 % for selected
output 0 ... 20 mA; 0.3 % for selected output 0 ... 10 V and from an input
voltage > 50 mV. For an input voltage < 50 mV, an offset of max. 20 ms is
effective at the output.
Siemens LV 1 T · 2006 7/113