English
Language : 

ISL6329 Datasheet, PDF (22/38 Pages) Intersil Corporation – Dual PWM Controller Powering AMD SVI Split-Plane Processors
ISL6329
the lower MOSFET to control the output voltage until the
overvoltage event ceases or the input power supply cuts off. For
complete protection, the low side MOSFET should have a gate
threshold well below the maximum voltage rating of the
load/microprocessor.
In the event that during normal operation if the PVCC, VCC or
GVOT voltage falls back below the POR threshold, the pre-POR
overvoltage protection circuitry reactivates to protect from any
more pre-POR overvoltage events.
Undervoltage Detection
The undervoltage threshold is set at VDAC - 300mV typical. When
the output voltage (VSEN-RGND) is below the undervoltage
threshold, PGOOD gets pulled low. No other action is taken by the
controller. PGOOD will return high if the output voltage rises
above VDAC - 250mV typical.
Overcurrent Protection
The ISL6329 takes advantage of the proportionality between the
load current and the average current, IAVG, to detect an
overcurrent condition. See “Continuous Current Sampling” on
page 14 and “Channel-Current Balance” on page 15 for more
detail on how the average current is measured. Once the average
current exceeds 100µA, a comparator triggers the converter to
begin overcurrent protection procedures.
The overcurrent trip threshold is dictated by the DCR of the
inductors, the number of active channels, the DC gain of the
inductor RC filter and the RISEN resistor. The overcurrent trip
threshold is shown in Equation 21.
IOCP
=
100
μ
A
⋅
N---
K
⋅
-R----I--S----E----N--
DCR
⎛
–⎜
⎝
V-----I--N-----–----N------Þ------V----O----U-----T-
2 Þ L Þ fS
⋅
-V---V-O---I-U-N---T--⎠⎟⎞
(EQ. 21)
Where:
K = -------R-----2--------
R1 + R2
See “Continuous Current Sampling” on
page 14.
fS = Switching Frequency
Equation 21 is valid for both the Core regulator and the
Northbridge regulator. This equation includes the DC load current
as well as the total ripple current contributed by all the phases.
For the Northbridge regulator, N is 1.
During soft-start, the overcurrent trip point is boosted by a factor
of 1.4. Instead of comparing the average measured current to
100µA, the average current is compared to 140µA. Immediately
after soft-start is over, the comparison level changes to 100µA.
This is done to allow for start-up into an active load while still
supplying output capacitor in-rush current.
OVERCURRENT PROTECTION SHUTDOWN
At the beginning of overcurrent shutdown, the controller sets all
of the UGATE and LGATE signals low, puts PWM3, PWM4, PWM5,
and PWM6 (if active) in a high-impedance state, and forces
VDDPWRGD low. This turns off all of the upper and lower
MOSFETs. The system remains in this state for fixed period of
12ms. If the controller is still enabled at the end of this wait
period, it will attempt a soft-start, as shown in Figure 14. If the
fault remains, the trip-retry cycles will continue until either the
fault is cleared or for a total of seven attempts. If the fault is not
cleared on the final attempt, the controller disables UGATE and
LGATE signals for both Core and Northbridge and latches off
requiring a POR of VCC to reset the ISL6329.
OUTPUT CURRENT, 50A/DIV
0A
OUTPUT VOLTAGE,
500mV/DIV
0V
3ms/DIV
FIGURE 14. OVERCURRENT BEHAVIOR IN HICCUP MODE
It is important to note that during soft-start, the overcurrent trip
point is increased by a factor of 1.4. If the fault draws enough
current to trip overcurrent during normal run mode, it may not
draw enough current during the soft-start ramp period to trip
overcurrent while the output is ramping up. If a fault of this type
is affecting the output, then the regulator will complete soft-start
and the trip-retry counter will be reset to zero. Once the regulator
has completed soft-start, the overcurrent trip point will return to
it’s nominal setting and an overcurrent shutdown will be initiated.
This will result in a continuous hiccup mode.
Note that the energy delivered during trip-retry cycling is much
less than during full-load operation, so there is no thermal
hazard.
CORE REGULATOR OVERCURRENT
The ISL6329 features a Dual Overcurrent Protection (OCP)
feature on the Core that allows AMD processors to “throttle” the
load current beyond the normal OCP threshold for brief periods of
time. These current spikes occur when idle processor cores are
enabled. Dual OCP is not enabled until soft-start is complete.
When the Core average sensed current, IAVG, exceeds 100μA, the
Core regulator does not immediately initiate overcurrent
protection shutdown. The ISL6329 will, instead, source an
amount of current out of the OCP pin that is equivalent to the
amount of sensed current that exceeds 100μA. A capacitor tied
between the OCP pin and ground will immediately begin
charging. If the voltage across the capacitor, and thus the voltage
on the OCP pin, exceeds 2V then the ISL6329 will immediately
initiate overcurrent protection shutdown. If IAVG decreases to a
level below 100μA prior to the voltage on the OCP pin exceeding
2V, then the OCP pin is internally pulled to ground and the
voltage on the OCP capacitor is discharged. If, at any time, the
average sensed current exceeds 145μA, the ISL6329 will
immediately initiate overcurrent protection shutdown.
It is recommended that the maximum current spike correspond
to an average sensed current level of 120μA. It is also
22
FN7800.0
April 19, 2011