E981.03
Table 38. KNX address register
Register Name
KNX_ADR_STAT
KNX_ADR_HIGH
KNX_ADR_LOW
Address
0x216
0x108
0x109
Description
status of the address
KNX subnet adress high byte
KNX subnet adress low byte
Table 39. Status of the KNX address
back to Table 8 Register Table
KNX_ADR_STAT
content
hard reset value
soft reset value
access
bit description
MSB
LSB
-
-
-
-
-
-
-
VALID
0
0
0
0
0
0
0
0
-
-
-
-
-
-
-
0
R
R
R
R
R
R
R
R/W 1)
VALID :
"1": the stored address is valid
"0": the stored address is invalid
the bit is set by the host by writing to the register or by using U_SetAddress service re-
quest
it is reset. If the Address is configured by SPI the User have to set this bit too.
- by the host by writing to the register and
- during soft reset
1) Access via UART service and SPI possible. In case of hard or soft reset the register is reset to the hard reset value or soft reset
value respectively.
Table 40. Telegram transmission register
Register Name
MAX_RST_CNT
KNX_TR_BUF_STAT
KNX_TX_LEN1
KNX_TX_LEN0
KNX_TR_BUF
KNX_RC_BUF
Address
0x217
0x215
0x218
0x219
0x000 …
0x107
0x1C0…
0x1FF
Description
number of retries in case of not acknowledge and busy
status of the transmit telegram buffer
length of the frame in the transmit buffer (bit 8) 1)
length of the frame in the transmit buffer (bits 7 ... 0) 1)
264 Byte transmit buffer
64 Byte receiving frame buffer
1) The length of the frame gives the number of bytes stored in the frame transmit buffer including all frame overhead.
Table 41. MAX_RST_CNT
back to Table 8 Register Table
MAX_RST_CNT
content
hard reset value
soft reset value
access
bit description
MSB
LSB
-
BUSY2 BUSY1 BUSY0 -
NACK2 NACK1 NACK0
0
0
1
1
0
0
1
1
-
0
1
1
-
0
1
1
R
R/W 1)
R/W 1)
R/W 1)
R
R/W 1)
R/W 1)
R/W 1)
ACK : number of retries in case of not acknowledge (either NACK on no ack frame)
BUSY : number of retries in case of busy (BUSY or simultaneously BUSY and NACK)
1) Access via UART service and SPI possible. In case of hard or soft reset the register is reset to the hard reset value or soft reset
value respectively.
Elmos Semiconductor AG reserves the right to change the detail specifications as may be required to permit improvements in the design of its products.
Elmos Semiconductor AG
Data Sheet
QM-No.: 25DS0046E.03
41/51