English
Language : 

E981.03 Datasheet, PDF (36/51 Pages) ELMOS Semiconductor AG – Autonomous MAC and individual physical address
KNX/ EIB TRANSCEIVER
PRODUCTION DATA - JAN 15, 2015
Table 21. Overview trigger register
Register Name
TRIGGER
TRIGGER_BUF
TRIGGER_MASK
TRIGGER_LEN1
TRIGGER_LEN0
Address
0x214
0x130 ...
0x148
0x150 ...
0x168
0x16B
0x16C
Description
wake-up register
25 byte trigger telegram buffer
25 byte trigger telegram mask buffer
length of trigger telegram (high byte)
length of trigger telegram (low byte)
E981.03
Table 22. Trigger register
back to Table 8 Register Table
TRIGGER
content
hard reset value
soft reset value
access
bit description
MSB
LSB
-
-
-
-
EVENT EN_OUT MASK_BUF BUF
0
0
0
0
0
1
0
0
-
-
-
-
-
1
0
0
R 1)
R 1)
R 1)
R 1)
R/W 1) R/W 1) R/W 1)
R/W 1)
EVENT :
"1": a trigger event was detected
"0": no trigger event detected
The EVENT bit is initially cleared. If the IC receives a triggering telegram on KNX bus it ac-
knowledges this telegram by sending a BUSY acknowledge on KNX bus and sets the EVENT
bit. Any further incoming triggering telegram will not be BUSY acknowledged by the IC as
long as the host does not clear the EVENT bit by writing a "0".
Acknowledge generation based on auto address mode is not affected by the EVENT bit
state.
EN_OUT :
"1": enable output stage (pull down disabled)
"0": disable output stage (output tri-state, pull down enabled)
MASK_BUF :
"1": the trigger mask buffer was written completely
"0": the trigger buffer was not written completely yet
BUF :
"1": the trigger buffer was written completely
"0": the trigger buffer was not written completely yet
Bits MASK_BUF and BUF are set by the E981.03 after successful upload using host UART
interface. They may be written by the host directly.
1) Access via UART service and SPI possible. In case of hard or soft reset the register is reset to the hard reset value or soft reset
value respectively.
Table 23. Alarm state register
Register Name
ALARM_STAT
ALARM_BUF
ALARM_LEN1
ALARM_LEN0
Address
0x213
0x110...
0x128
0x169
0x16A
Description
alarm status register
25 byte alarm telegram buffer
length of alarm telegram (high byte)
length of alarm telegram (low byte)
The alarm state register is used to signal the state of the alarm functionality and to control sending of the alarm
telegram. Reading the register is allowed any time using any interface. Writing to the register is only recommended
to clear the SENT bit and allow resending of the alarm telegram. A successful alarm telegram transmission is con-
firmed to the host by sending a L_Data.confirm service on host UART interface.
Table 24. Alarm status register Power supply registers
back to Table 8 Register Table
ALARM_STAT
MSB
LSB
content
-
-
-
-
-
PEND BUF
SENT
hard reset value 0
0
0
0
0
0
0
0
Elmos Semiconductor AG reserves the right to change the detail specifications as may be required to permit improvements in the design of its products.
Elmos Semiconductor AG
Data Sheet
QM-No.: 25DS0046E.03
36/51