BTS54040-LBF_15 Datasheet, PDF (21/67 Pages) Infineon Technologies AG – SPI Power Controller
BTS54040-LBF
Power Supply
5.1
Operation modes
BTS54040-LBF has the following operation modes:
• Stand-by mode
• Idle mode
• Ready mode
• Operative mode
• Limp Home mode
The transition between operation modes is determined according to these variables:
• logic level at LHI pin
• logic level at INn pins
• DCR.MUX bits state
• OUT.OUTn bits state
The state diagram including the possible transitions is shown in Figure 10. The behavior of BTS54040-LBF as
well as some parameters may change in dependence from the operation mode of the device. Furthermore, due
to the undervoltage detection circuitry which monitors VS and VDD supply voltages, some changes within the same
operation mode can be seen accordingly.
Power -up
Idle
DCR.MUX ≠ "111"
Stand-by
LHI = "low"
& INn = "low"
DCR.MUX = "111" or
VDD < VDD(PO) or
HWCR.RST = "1"
LHI = "high"
OUT.OUTn = "1"
or INn = "high"
OUT.OUTn = "0"
& INn = "low"
(VD(HDW<CVR.DDR(PSOT)
&
=
INn
"1"
=
&
I„Nlonw“=) o„lorw“)
OUT.OUTn = "1
or INn = "high"
"
OUT.OUTn = "0" or
(VDD < VDD(PO) & INn = "low") or
HWCR.RST = "1"
Operative
DCR.MUX ≠ "111"
Ready
LHI = "low"
& INn = "high"
DCR.MUX = "111" or
(VDD < VDD(PO ) & INn = "high") or
(HWCR.RST = "1" & INn = "high")
LHI = "high"
LHI = "high"
Note: Registers which are not mentioned are considered to be in default state
LHI = "high"
Limp Home
PowerSupply_OpModes.emf
Figure 10 Operation Mode state diagram
There are three parameters describing the behavior of BTS54040-LBF:
• status of output channels
• status of SPI registers
• status of SPI communication
It is necessary to set DCR.MUX to a value different from 111B to command a switch ON of one or more channels.
In alternative it is necessary to set the LHI to “high” - in this case the logic state of the Input pins is reflected to the
outputs (if there is no undervoltage condition on VS supply).
Data Sheet
21
Rev. 2.1, 2014-12-05