English
Language : 

CO4011A-FL Datasheet, PDF (14/37 Pages) List of Unclassifed Manufacturers – Single Chip CANopen Controller for Remote I/O
CO4011A-FL
Single Chip CANopen Controller for Remote I/O
By read access to object 1010h Subindex 1, the
device responds with SDO data 00000001h indi-
cating that storing of data is only done on command.
Note:
Writing to this objected is only allowed in pre-
operational mode.
Index 1011 : Restore Default Parameters
With this object the default values of parameters
according to the communication or device profile are
restored. By read access the device provides infor-
mation about its capabilities to restore these values.
Several parameter groups are distinguished:
Sub-Index 0 contains the largest Sub-Index that is
supported.
Writing to Sub-Index 1 restores all parameters that
can be restored.
In order to avoid the restoring of default parameters
by mistake, restoring is only executed when a
specific signature is written to the appropriate sub-
index. (This means that the signature is transferred
as data bytes 4 to 7 in the CAN message of the
corresponding SDO protocol.
The signature is "load".
MSB
d
a
o
64h
61h
6Fh
LSB
l
6Ch
On reception of the correct signature on sub-index 1
the device restores the parameters and then
confirms the SDO transmission (initiate download
response). If the storing failed, the device responds
with an abort SDO transfer (abort code: 0606
0000h).
If a wrong signature is written, the device refuses to
store and responds with Abort SDO Transfer
(Abort code: 0800 002x h).
The default values are set valid after the device is
reset (reset node) or power cycled. If the device
requires storing on command (see Object 1010h),
the appropriate command has to be executed after
the reset if the default parameters are to be stored
permanently.
Index
Name
Description
Data Type
1011h
Restore Default Parameters
-
Structure
Index
1011h Subindex 0
Name
Largest SubIndex supported
Description -
Data Type
Unsigned char
Access modes RO
PDO Mapping No
Value Range 1
Default Value 1
Index
1011h Subindex 1
Name
Restore All Parameters
Description Writing to this object restores the
default values to the dictionary.
Data Type
Unsigned 32
Access modes RW
PDO Mapping No
Value Range Signature "load"
Default Value -
By read access to object 1011h Subindex 1, the
device responds with SDO data 00000001h indi-
cating that restoring of default data is available.
Note:
Writing to this objected is only allowed in pre-
operational mode.
Index 1014 : COB-ID Emergency
Identifier of Can Object for the emergency
messages.
Index
1014h
Name
COB-ID Emergency
Description -
Data Type
Unsigned 32
Access modes RW
PDO Mapping No
Value Range -
Default Value 80h + Node-ID
frenzel + berg elektronik – Maximilianstr. 28 – 89231 Neu-Ulm – Germany - phone +49(0)731/970 570 - fax +49(0)731/970 5739 – www.frenzel-berg.de
Page 14 of 14
Revision 1.39
May/19/2003