1.4 QuickStart Configuration
Enter
Down
Up
Figure 2
Transmitter Keypad & Display
➅ 20 mA Level
Liquid
Level
➀ Process
S.G.
➁ Operating
Temp.
Displacer
➄ 4 mA Level
➃ Level Offset
The E3 Modulevel transmitter comes configured with
default values from the factory but can be reconfigured
in the shop. The minimum configuration instructions
required in the field follow. Use the information from
the operating parameters table in Section 1.1.2 before
beginning configuration.
1. Power up the transmitter.
The display changes every 5 seconds to show one of four
values: Status, Level (or IfcLevel or SpecGrav), %Output,
and Loop current.
2. Remove the cover of the lower electronic compartment.
3. Use the and keys to move from one step of the
configuration program to the next step, see Figure 2.
4. Press the key. The last character in
the first line of the display changes to
an exclamation point (!).
LvlUnits!
xxx
5. Use the and keys to increase or decrease the value in
the display or to scroll through the choices.
6. Press the key to accept a value and move to the next step
of the configuration program (the default password is 0).
7. After entering the last value, allow 10 seconds before
removing power from the transmitter.
The following two configuration entries are the minimum required for
configuration (the default password is 0 from the LCD/keypad).
Figure 3
Tank Top Mounted
Installation
Œ
Proc SG
(xxx)
Enter the actual specific gravity of the process liquid at
operating temperature (N/A for Interface or Density).
➅
20 mA Level
➄
4 mA Level
➀ Process S.G.
Liquid
Level
➃
Level Offset
➁ Operating
Temp.

OperTemp
xxx
Enter the actual operating temperature of the process
The following four parameters must be entered if the default values are
not satisfactory.
Ž
LvlUnit
(select)
Select the desired level units of measure
(inches, cm, m, feet). (Default is inches).

➂
 In, cm, m, or ft.
Lvl Ofst
(xxx)
Set 4mA
xxx.x
Enter the desired level reading when level is at the calibrated
zero reference (typically bottom of the displacer). (Default is
Zero).
Enter the level value (0%-point) for the 4 mA point. (Default
is 0 for level and interface).
Figure 4
Chamber Type Installation
Side-Side Process Connections
‘ Set 20mA
xxx.x
Enter the level value (100%-point) for the 20 mA point.
(Default is full level range).
6
48-635 E3 Modulevel Displacer Level Transmitter