1.0 QuickStart Installation
1.1 Getting Started
1.1.1 Equipment and Tools
No special equipment or tools are required to install E3
Modulevel. The following items are recommended:
• Wrenches, flange gaskets and flange bolting appropriate for
process connection(s)
• Flat-blade screwdriver
• Level
• 1⁄8" Allen wrench
• Power supply
• Digital multimeter
• 250 to 450 ohm resistor for HART communication
1.1.2 Configuration Information
Some key information is needed to configure the E3
Modulevel transmitter. Complete the following operating
parameters table before beginning configuration.
Display Question
Answer
LvlUnits What units of measurement will be used?
Lvl Ofst
Proc SG
What is the desired level reading when the
level is at the calibrated zero reference
(typically bottom of the displacer)?
What is the actual SG of the process liquid at
operating temperature?
OperTemp What is the actual operating temperature?
Set 4mA
Set 20mA
What should the level reading be at the 4 mA
set point?
What should the level reading be at the 20
mA set point?
1.2 QuickStart Mounting
NOTE: Confirm the style and process connection size/type of the
E3 Modulevel transmitter. Ensure it matches the requirements
of the installation before continuing with the QuickStart instal-
lation.
1.2.1 Tank Top
1. If applicable, adjust and trim the adjustable hanger cable
assembly to the required length and mount it between the
stem and displacer.
4
48-635 E3 Modulevel Displacer Level Transmitter