The numbers are not shown on the display. They are pro-
vided as a reference.
The third column provides the actions to take when
configuring the transmitter. Additional information or an
explanation of an action is given in the fourth column.
Configuration tips:
If “Calselct” is Factory, Factory Cal Menu is available for
viewing only. Only calibration parameters in User Cal
Menu can be changed by the user.
To capture the current sensor value, press and
simultaneously.
PV = Primary Variable = Level or Interface Level or Density
(depending on Measurement Type).
2.6.5.1 Measurement Type: Level
Display
*Status*
1
*Level *
*% Out *
* Loop *
2
Level
xx.xx lu
3
% Output
xx.x %
4
Loop
xx.xx mA
5
LvlUnits
(select)
6
Proc SG
x.xxx sg
7
OperTemp
xxx F
8
Set 4mA
xx.xx lu
9
Set 20mA
xx.xx lu
10
Lvl Ofst
xx.xx lu
Action
Transmitter Display
Comment
Transmitter Display
(Alternate Home Menu)
Transmitter Display
(Alternate Home Menu)
Transmitter Display
(Alternate Home Menu)
Select the level units
of measure
Select cm, inches, feet, meters
Enter the specific gravity of the Adjusts factory calibration for actual specific gravity
process liquid at operating temp. (limited by SG range of spring)
Enter the Process Operating Adjusts factory calibration for actual temperature
Temperature
(limited by maximum temperature rating of model)
Enter the level value for 4 mA Specify level at 4 mA
set point
Enter the level value for
20 mA set point
Specify level at 20 mA
Enter desired output when Minimum offset = -(displacer length)
level is at the calibrated zero Zero reference is typically bottom of displacer or centerline of
reference
bottom-side process connection.
11
Damping
xx s
Enter time constant of
desired damping
0 to 45 sec
12
Fault
(select)
Select loop current value in Select from 3.6 mA, 22 mA or Hold
presence of a fault
13
Poll Adr
xx
Enter HART polling address If multidrop is not in use, poll address must = 0
number
14
Trim Lvl
xx.xx lu
Enter value to adjust Level
reading
Fine tune level reading
48-635 E3 Modulevel Displacer Level Transmitter