E3A-MA3A-H11 Datasheet, PDF (19/48 Pages) Magnetrol International, Inc. – Digital E3 Modulevel with HART® and PACTware™ Communications Liquid Level Displacer Transmitter
2.6.5.1 Measurement Type: Level Only (cont.)
Display
Action
Comment
37b
User Cal Menu Press to display the User CalSelct = User
Calibration sub-menu
Submenu below
38
AdjSnrLo
Diagnostic Display
39
AdjSnrHi
Diagnostic Display
40
Conv Fct
xxxx
Diagnostic Display
41
Scl Ofst
xxx
Diagnostic Display
42
LVDT%
xx.xx %
Diagnostic Display
43
Chan 0
Diagnostic Display
44
Chan 1
Diagnostic Display
45
NSP Value
Diagnostic Display
46
ElecTemp
xxx F
Diagnostic Display
47
Max Temp
xxx F
Diagnostic Display
48
Min Temp
xxx F
Diagnostic Display
Present temperature in electronics compartment
Maximum electronics temperature recorded
Minimum electronics temperature recorded
2.6.5.1 Measurement Type: Level Only: Factory (display only) or User Calibration sub-menu
Display
1
LVDT%
xx.xx %
2
Calib SG
x.xxx sg
3
DrySensr
xx.xx %
4
SnrCalLo
xx.xx %
5
LvlCalLo
xx.xx lu
6
Set 4mA
xx.xx lu
7
SnrCalHi
xx.xx %
8
LvlCalHi
xx.xx lu
9
Set 20mA
xx.xx lu
10
Escape
Action
Diagnostic display
Comment
Factory set
Factory calibration menu only
Enter or capture sensor
output for Dry Sensor
Enter or capture sensor
output for Low Cal Point
Enter Level value
corresponding to SnrCalLo
Enter the level value for
4 mA set point
Enter or capture sensor
output for High Cal Point
Enter Level value
corresponding to SnrCalHI
Enter the level value for
20 mA set point
Press to exit Calibration
sub-menu; Returns to
Factory Menu
Press and
sensor output
Press and
sensor output
simultaneously to capture current
simultaneously to capture current
Specify level at 4 mA (User Cal menu only)
Press and
sensor output
simultaneously to capture current
Specify level at 20 mA (User Cal menu only)
48-635 E3 Modulevel Displacer Level Transmitter