2.6.5.2 Measurement Type: Interface Level (cont.): Factory (display only) or User Calibration sub-menu
Display
1
LVDT%
xx.xx %
2
DrySensr
xx.xx %
3
SnrCalLo
xx.xx %
4
LvlCalLo
xx.xx lu
5
Set 4mA
xx.xx lu
6
SnrCalHi
xx.xx %
7
LvlCalHi
xx.xx lu
8
Set 20 mA
xx.xx lu
9
Escape
Action
Diagnostic display
Comment
Enter or capture sensor
output for Dry Sensor
Enter or capture sensor
output for Low Cal Point
Enter IfcLevel value corre-
sponding to SnrCalLo
Enter the IfcLevel value for
4 mA set point
Enter or capture sensor
output for High Cal Point
Enter IfcLevel value corre-
sponding to SnrCalHI
Enter the IfcLevel value for
20 mA set point
Press to exit Calibration
sub-menu; Returns to
Factory Menu
Press and
sensor output
Press and
sensor output
simultaneously to capture current
simultaneously to capture current
Assigns Level value to 4 mA loop value (User Cal menu only)
Press and simultaneously
to capture current sensor output
Assigns Level value to 20 mA loop value (User Cal menu only)
2.6.5.3 Measurement Type: Density
Display
*Status*
1
*SG *
*% Out *
* Loop *
2
SpecGrav
x.xx sg
3
% Output
xx.x %
4
Loop
xx.xx mA
5
OperTemp
xxx F
6
Set 4mA
xx.xx sg
7
Set 20mA
xx.xx sg
8
Damping
xx s
9
Fault
(select)
10
Poll Adr
xx
11
Trim SG
x.xx sg
12
Trim 4
xxxx
Action
Transmitter Display
Comment
Transmitter Display
(Alternate Home Menu)
Transmitter Display
(Alternate Home Menu)
Transmitter Display
(Alternate Home Menu)
Enter the Process Operating Adjusts factory calibration for actual temperature
Temperature
(limited by maximum temperature rating of model)
Enter the SpecGrav value for Assigns specific gravity value to 4 mA loop value
4 mA set point
Enter the SpecGrav value for Assigns specific gravity value to 20 mA loop value
20 mA set point
Enter time constant of
desired damping
0 to 45 sec
Select loop current value in Select from 3.6 mA, 22 mA or Hold
presence of a fault
Enter HART polling address If multidrop is not in use, poll address must = 0
number
Enter value to adjust SG
reading
Fine tune SpecGrav reading
Fine tune 4 mA point
Adjust setting (0 – Trim 20 value) to output exactly 4.0 mA
22
48-635 E3 Modulevel Displacer Level Transmitter