E3A-MA3A-H11 Datasheet, PDF (20/48 Pages) Magnetrol International, Inc. – Digital E3 Modulevel with HART® and PACTware™ Communications Liquid Level Displacer Transmitter
2.6.5.2 Measurement Type: Interface Level
Display
*Status*
1
*IfcLvl*
*% Out *
* Loop *
2
IfcLevel
xx.xx lu
3
% Output
xx.x %
4
Loop
xx.xx mA
5
LvlUnits
(select)
6
Oper Temp
xxx F
7
Set 4mA
xx.xx lu
8
Set 20mA
xx.xx lu
9
Lvl Ofst
xxx.xx lu
10
Damping
xx s
11
Fault
(select)
12
Poll Adr
xx
13
Trim Lvl
xx.xx lu
14
Trim 4
xxxx
15
Trim 20
xxxx
16
Loop Tst
xx.x mA
17
Capture
4.00 mA
Action
Transmitter Display
Comment
Transmitter Display
(Alternate Home Menu)
Transmitter Display
(Alternate Home Menu)
Transmitter Display
(Alternate Home Menu)
Select the level units of
measure
Enter the Process
Operating Temperature
Enter the IfcLevel value for
4 mA set point
Enter the IfcLevel value for
20 mA set point
Enter desired output when
level is at the calibrated zero
reference
Select cm, inches, feet, meters
Adjusts factory calibration for actual temperature
(limited by maximum temperature rating of model)
Assigns Level value to 4 mA loop value
Assigns Level value to 20 mA loop value
Minimum offset = -(displacer length)
Zero reference is typically bottom of displacer or centerline of
bottom-side process connection.
Enter time constant of
desired damping
Select loop current value in
presence of a fault
Enter HART polling address
number
Enter value to adjust Level
reading
Fine tune 4 mA point
0 to 45 sec
Select from 3.6 mA, 22 mA or Hold
If multidrop is not in use, poll address must = 0
Fine tune IfcLevel reading
Adjust setting (0 – Trim 20 value) to output exactly 4.0 mA
Fine tune 20 mA point
Adjust setting (Trim 4 value – 4095) to output exactly 20.0 mA
Enter a mA output value to
test loop
Pressing in Data Entry
Mode captures current level
output as 4.00 mA Set Point
Raise interface level to desired 4 mA point on the displacer.
Press and to “capture” this liquid level as your 4 mA
point.
In Data Entry Mode, can
Set second level point between 8.00 mA and 20.00 mA. Raise
18
Capture
20.00 mA
adjust loop value to corre- interface level to a second level point on the displacer. Press
spond to current level output and to “capture” this interface level as your upper loop
for setting 20.00 mA Set Point value between 8.00 and 20.00 mA.
19
New Pass
xxx
Enter new password (0 – 255) Displays encrypted value of present password
Default value = 0
20
Language
(select)
Select from English, Spanish, Language choice for LCD display
French, German
21
E3 ModHT
Ver 1.0
Transmitter Display
Product identification
Firmware version
22
DispFact
(select)
Select “Yes” to display factory Selecting “No” takes you back to beginning of menu
parameter menu as below
20
48-635 E3 Modulevel Displacer Level Transmitter