English
Language : 

ISL6398 Datasheet, PDF (27/57 Pages) Intersil Corporation – Programmable soft-start rate and DVID rate
ISL6398
VOUT
VSEN_OVP
+
OV
-
VOUT
VCC
VSEN_OVP
+
OV
-
DAC + OVP
DAC + OVP
A. INCREASED OVP
B. REDUCED OVP
FIGURE 18. EXTERNAL PROGRAMMABLE OVP
Furthermore the regulation loop (VSEN pin) and the OVP sense
(VSEN_OVP) are separated paths, the OVP level can be
programmed higher or lower than the target, as in Figure 18. The
OVP level cannot be scaled too close to DAC to ensure that the
OVP is not triggered during transient response and start-up.
In addition, the ISL6398 also provides early OVP warning; when it
is triggered, it asserts STATUS_WORD (79h Upper Byte, Bit7) and
SM_PMALERT#. It however does not shutdown the system,
assert STATUS_BYTE, or pull VR_RDY low. Disregard this if both
STATUS_WORD and SM_PMALERT# are not used or disable OVP
Warning as needed via DFh.
Undervoltage Protection
When the output voltage drops below a level programmed by
PMBus (E1[3:0]), the VR_RDY is pulled low. The controller can
respond to UVP with two different options programmed by
PMBus (E1[6]): 1) acts as a OCP event, hiccup the output with
9ms duration and pull VR_RDY low; or 2) acts like a PGOOD, pull
VR_RDY low, monitor only. To avoid faulty triggering at
transient/DVID events, the UVP delay is programmable by
E1[5:4]. Furthermore, the UVP is not enabled during soft-start
and also can be disabled by DF[5]. The ISL6398 also provides
early UVP warning; when it is triggered, it asserts STATUS_WORD
(79h Upper Byte, Bit7) and SM_PMALERT#. It however does not
shutdown the system, assert STATUS_BYTE or pull VR_RDY low.
Disregard this if both STATUS_WORD and SM_PMALERT# are not
used or disable UVP Warning as needed via DFh.
Overcurrent Protection
The ISL6398 has two levels of overcurrent protection. Each phase
is protected from a sustained overcurrent condition by limiting its
peak current, while the combined phase currents are protected on
an instantaneous basis.
For the individual channel overcurrent protection, the ISL6398
continuously compares the sensed peak current (~50ns filter)
signal of each channel with the reference current (ICL, typically
125µA, programmable via F4[5:3] and F3[2:0]). If one channel
current exceeds the reference current, the ISL6398 will pull PWM
signal of this channel to low for the rest of the switching cycle.
This PWM signal can be turned on next cycle if the sensed
channel current is less than the reference current. The peak
current limit of individual channels will only use cycle-by-cycle
current limiting and will not trigger the converter to shut down.
In instantaneous protection mode, the ISL6398 utilizes the
sensed average current IAVG to detect an overcurrent condition.
Refer to “Current Sensing” on page 18 for more details on how
the average current is measured. The average current is
continually compared with a reference current (typically 100µA,
programmable via F2[2:0]), as shown in Figure 17. Once the
average current exceeds the reference current, a comparator
triggers the converter to shut down. In addition, the current out of
the IMON pin is equal to the sensed average current IAVG. With a
resistor from IMON to GND, the voltage at IMON will be
proportional to the sensed average current and the resistor value.
The ISL6398 continuously monitors the voltage at the IMON pin. If
the voltage at the IMON pin is higher than 3.0V, a precision
comparator triggers the overcurrent shutdown. Since the internal
current comparator has wider tolerance than the voltage
comparator, the IMON voltage comparator is the preferred one for
OCP trip. Therefore, the resistor between IMON and GND can be
scaled such that the overcurrent protection threshold is tripping
lower than 100µA. For example, the overcurrent threshold for the
sensed average current IAVG can be set to 95µA by using a 31.5k
resistor from IMON to GND. Thus, the internal 100µA comparator
might only be triggered at its lower corner. However, IMON OCP trip
should NOT be too far away from 125µA, which is used for
cycle-by-cycle protection and inductor saturation.
OUTPUT CURRENT
0A
OUTPUT VOLTAGE
0V
2ms/DIV
FIGURE 19. OVERCURRENT BEHAVIOR IN HICCUP MODE
FSW = 500kHz
At the beginning of overcurrent shutdown, the controller places all
PWM signals in a high-impedance state, commanding the Intersil
MOSFET driver ICs to turn off both upper and lower MOSFETs. The
system remains in this state a period of 9ms. If the controller is still
enabled at the end of this wait period, it will attempt a soft-start. If
the fault remains, the trip-retry cycles will continue indefinitely
(as shown in Figure 19) until either controller is disabled or the fault
is cleared. Note that the energy delivered during trip-retry cycling is
much less than during full-load operation, so there is no thermal
hazard during this kind of operation.
Thermal Monitoring (VR_HOT#)
VR_HOT# indicates the temperature status of the voltage
regulator. VR_HOT# is an open-drain output, and an external
pull-up resistor is required. This signal is valid only after the
controller is enabled.
The VR_HOT# signal can be used to inform the system that the
temperature of the voltage regulator is too high.
Submit Document Feedback 27
FN8575.1
August 13, 2015