English
Language : 

CP5.241 Datasheet, PDF (9/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
9. EFFICIENCY AND POWER LOSSES
AC 100V
AC 120V
AC 230V
Efficiency
Typ.
92.9%
93.6%
94.3%
At 24V, 5A
Typ.
92.7%
93.5%
94.5%
At 24V, 6A (Power Boost)
Average efficiency*)
Typ.
91.3%
91.7%
92.0%
25% at 1.25A, 25% at 2.5A,
25% at 3.75A. 25% at 5A
Power losses
Typ.
1.5W
1.5W
1.4W
At 24V, 0A
Typ.
4.6W
4.4W
4.1W
At 24V, 2.5A
Typ.
9.2W
8.2W
7.3W
At 24V, 5A
Typ.
11.3W
9.8W
8.4W
At 24V, 6A (Power Boost)
*) The average efficiency is an assumption for a typical application where the power supply is loaded with 25% of the nominal load for 25%
of the time, 50% of the nominal load for another 25% of the time, 75% of the nominal load for another 25% of the time and with 100%
of the nominal load for the rest of the time.
Fig. 9-1 Efficiency vs. output current at 24V,
typ
Efficiency
95%
(c)
94
(b)
93
(a)
92
91
(a) 100Vac
90
(b) 120Vac
(c) 230Vac
89
88
Output Current
87
1
2
3
4
5 6A
Fig. 9-2 Losses vs. output current at 24V, typ.
Power Losses
12W
10
8
6
4
2
0
01
(a) 100Vac
(a)
(b) 120Vac
(b)
(c) 230Vac
(c)
Output Current
2 3 4 5 6A
Fig. 9-3 Efficiency vs. input voltage at 24V,
5A, typ.
Efficiency
95%
94
93
92
91
90
89
100 120
Input Voltage
180
230 264Vac
Fig. 9-4 Losses vs. input voltage at 24V, 5A,
typ.
Power Losses
11W
10
9
8
7
6
5
100 120
Input Voltage
180
230 264Vac
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/26