CP5.241 Datasheet, PDF (5/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
4. DC-INPUT
DC input
DC input range
DC input current
Allowed Voltage L/N to Earth
Turn-on voltage
Shut-down voltage
Nom.
Min.
Typ.
Max.
Typ.
Typ.
DC 110-300V
88-300Vdc
1.21 / 0.43A
360Vdc
74Vdc
68Vdc
-20%/+0%
Continuous operation
At 110 / 300Vdc, at 24V, 5A
Continuous, IEC 62477-1
Steady state value
Steady state value
Fig. 4-1 Wiring for DC Input
Battery
Power Supply
+
AC
L
N
+
PE
-
Load
-
DC
Instructions for DC use:
a) Use a battery or a similar DC source. A supply from the
intermediate DC-bus of a frequency converter is not
recommended and can cause a malfunction or damage
the unit.
b) Connect +pole to L and –pole to N.
c) Connect the PE terminal to an earth wire or to the
machine ground.
5. INPUT INRUSH CURRENT
An active inrush limitation circuit (NTCs, which are bypassed by a relay contact) limits the input inrush current after
turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
Inrush current
Inrush energy
Max.
Typ.
Typ.
Max.
AC 100V
8Apeak
5Apeak
5Apeak
0.4A²s
AC 120V
7Apeak
4Apeak
5Apeak
0.5A²s
AC 230V
7Apeak
4Apeak
6Apeak
1A²s
At 40°C, cold start
At 25°C, cold start
At 40°C, cold start
At 40°C, cold start
Fig. 5-1 Typical turn-on behaviour at nominal
load, 120Vac input and 25°C ambient
Input
50ms/DIV
4A
current
2A/DIV
Input
voltage
200V/DIV
Fig. 5-2 Typical turn-on behaviour at nominal
load, 120Vac input and 25°C ambient
Input
4A
current
2A/DIV
50ms/DIV
Input
voltage
200V/DIV
Output voltage 20V/DIV
Output voltage 20V/DIV
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.