CP5.241 Datasheet, PDF (8/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
7. HOLD-UP TIME
Hold-up Time
Typ.
Min.
Typ.
Min.
AC 100V
50ms
40ms
25ms
20ms
AC 120V
50ms
40ms
25ms
20ms
AC 230V
50ms
40ms
25ms
20ms
At 24V, 2.5A, see Fig. 7-1
At 24V, 2.5A, see Fig. 7-1
At 24V, 5A, see Fig. 7-1
At 24V, 5A, see Fig. 7-1
Fig. 7-1 Hold-up time vs. input voltage
Hold-up Time
60ms
50
a) 24V 2.5A typ. c) 24V 5A typ.
b) 24V 2.5A min. d) 24V 5A min.
a
40
b
30
c
20
d
10
Input Voltage
0
90 120 155 190 230Vac
Fig. 7-2 Shut-down behavior, definitions
Input
Voltage
Zero Transition
Output
Voltage
Hold-up Time
- 5%
8. DC-OK RELAY CONTACT
The DC-OK relay contact reports an output terminal voltage above 90% of the adjusted output voltage.
Contact closes
Contact opens
Switching hysteresis
Contact ratings
Isolation voltage
As soon as the output voltage reaches typ. 90% of the adjusted output voltage level.
As soon as the output voltage dips more than 10% below the adjusted output voltage.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored.
Typically 0.7V
Maximal 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A, resistive load
Minimal permissible load: 1mA at 5Vdc
See dielectric strength table in section 18.
Fig. 8-1 DC-ok relay contact behavior
VOUT = VADJ
10%
0.9* VADJ
<
>
1ms
1ms
100ms
open
closed
open
closed
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/26