CP5.241 Datasheet, PDF (10/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
10. LIFETIME EXPECTANCY
The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by
the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and
is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors
only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated
theoretical lifetime which can be used to compare devices.
Lifetime expectancy
AC 100V
265 000h
748 000h
128 000h
363 000h
81 000h
228 000h
AC 120V
270 000h
764 000h
143 000h
405 000h
96 000h
271 000h
AC 230V
274 000h
775 000h
166 000h
469 000h
119 000h
336 000h
At 24V, 2.5A and 40°C
At 24V, 2.5A and 25°C
At 24V, 5A and 40°C
At 24V, 5A and 25°C
At 24V, 6A and 40°C
At 24V, 6A and 25°C
11. MTBF
MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h
means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not
be determined if the failed unit has been running for 50 000h or only for 100h.
For these types of units the MTTF (Mean Time To Failure) value is the same value as the MTBF value.
MTBF SN 29500, IEC 61709
MTBF MIL HDBK 217F
AC 100V
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
AC 120V
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
AC 230V
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
At 24V, 5A and 40°C
At 24V, 5A and 25°C
At 24V, 5A and 40°C;
Ground Benign GB40
At 24V, 5A and 25°C;
Ground Benign GB25
At 24V, 5A and 40°C;
Ground Fixed GF40
At 24V, 5A and 25°C;
Ground Fixed GF25
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
10/26