English
Language : 

CP5.241 Datasheet, PDF (1/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
POWER SUPPLY
ƒ AC 100-240V Wide-range Input
ƒ DC 110-300V Wide-range Input
ƒ Width only 32mm
ƒ Efficiency up to 94.3%
ƒ Excellent Partial Load Efficiency
ƒ 20% Output Power Reserves
ƒ Easy Fuse Breaking – 3 times nominal current for 12ms
ƒ Safe HiccupPLUS Overload Mode
ƒ Active Power Factor Correction (PFC)
ƒ Minimal Inrush Current Surge
ƒ Full Power Between -25°C and +60°C
ƒ DC-OK Relay Contact
ƒ 3 Year Warranty
GENERAL DESCRIPTION
The Dimension CP-Series are cost optimized power
supplies without compromising quality, reliability and
performance. The CP-Series is part of the DIMENSION
power supply family.
The CP5.241 power supplies come with three connection
terminal options: screw, spring-clamp or push-in
terminals, which are optimized for automated wiring.
The CP5.241-C1 is equipped with conformal coated pc-
boards preferred for the use in harsh environments.
The most outstanding features of these units are the
small size, the high efficiency, the electronic inrush
current limitation, active PFC and the wide operational
temperature range. The devices have a power reserve of
20% included, which may even be used continuously at
temperatures up to +45°C. Additionally, they can deliver
3 times the nominal output current for 12ms which
helps to trip fuses on faulty output branches.
High immunity to transients and power surges as well as
low electromagnetic emission, a DC-OK signal contact
for remote monitoring, and a large international
approval package for a variety of applications makes
this unit suitable for nearly every situation.
ORDER NUMBERS
Power Supply CP5.241
CP5.241-C1 Conformal coated pc-boards
CP5.241-S1 Spring-clamp terminals
CP5.241-S2 Push-in terminals
Mechanical Accessory
ZM6.WALL Wall/Panel mount bracket
SHORT-FORM DATA
Output voltage
Adjustment range
Output current
Input voltage AC
Mains frequency
Input current AC
Power factor
Input voltage DC
Input current DC
AC Inrush current
Efficiency
Losses
Hold-up time
Temperature range
Size (WxHxD)
Weight
DC 24V
Nominal
24 - 28V
Factory setting 24.1V
6.0 - 5.1A
Below +45°C ambient
5.0 – 4.3A
At +60°C ambient
3.8 – 3.2A
At +70°C ambient
Derate linearely between +45°C and +70°C
AC 100-240V -15%/+10%
50-60Hz
±6%
1.09 / 0.6A
At 120 / 230Vac
0.98 / 0.91
At 120 / 230Vac
DC 110-300V -20%/+0%
1.21 / 0.43A
At 110/300Vdc
4 / 4A
At 120 / 230Vac
93.6 / 94.3%
At 120 / 230Vac
8.2 / 7.3W
At 120 / 230Vac
25ms
-25°C to +70°C
32x124x102mm Without DIN-rail
440g / 0.97lb
MARKINGS
IND. CONT. EQ.
UL 508, planned
UL 60950-1, planned
Marine, planned
IECEx
ATEX
Class I Div 2, planned
planned
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
1/26