CP5.241 Datasheet, PDF (15/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
Switching Frequencies
PFC converter
Main converter
Auxiliary converter
70kHz to 130kHz
60kHz to 140kHz
60kHz
Input voltage and output power dependent
Output load dependent
Fixed frequency
16. ENVIRONMENT
Operational temperature 1) -25°C to +70°C (-13°F to 158°F)
Reduce output power according to Fig. 15-1
Storage temperature
-40°C to +85°C (-40°F to 185°F)
For storage and transportation
Output de-rating
1.6W/°C
3W/°C
Between +45°C and +60°C (113°F to 140°F)
Between +60°C and +70°C (140°F to 158°F)
Humidity
5 to 95% r.h.
According to IEC 60068-2-30
Do not energize while condensation is present.
Vibration sinusoidal 2)
2-17.8Hz: ±1.6mm; 17.8-500Hz: 2g
2 hours / axis
According to IEC 60068-2-6
Shock 2)
30g 6ms, 20g 11ms
According to IEC 60068-2-27
3 bumps / direction, 18 bumps in total
Altitude
0 to 2000m (0 to 6 560ft)
Without any restrictions
2000 to 6000m (6 560 to 20 000ft)
Reduce output power or ambient temperature
according to Fig. 15-2
Altitude de-rating
7.5W/1000m or 5°C/1000m
Above 2000m (6500ft), see Fig. 15-2
Over-voltage category
III
According to IEC 62477-1 for altitudes up to
2000m
II
For altitudes from 2000m to 6000m
Degree of pollution
2
According to IEC 62477-1, not conductive
LABS compatibility
The unit does not release any silicone or other LABS-critical substances and is suitable for
use in paint shops.
Audible noise
Some small audible noise will be emitted from the power supply
Corrosive gases
ISA-71.04-1985, Severity Level G3, IEC 60068-2-60 Test Ke Method 4
Audible noise
Some small audible noise will be emitted from the power supply
1) Operational temperature is the same as the ambient or surrounding temperature and is defined as the air temperature 2cm below the unit.
2) Tested in combination with DIN-Rails according to EN 60715 with a height of 15mm and a thickness of 1.3mm and standard orientation.
Fig. 16-1 Output current vs. ambient temp.
Allowed Output Current at 24V
6A
B
A
5A
4A
3A
2A
A... 85 to 264Vac, continuous
1A B... short term
0
-25
0
20 40 60 70°C
Ambient Temperature
Fig. 16-2 Output current vs. altitude
Allowed Output Current at 24V
6A
D
5A
C
B
4A
A
3A
A... Tamb < 60°C
2A
B... Tamb < 50°C
C... Tamb < 40°C
1A
D... Short term
0
0
2000m 4000m 6000m
Altitude
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
15/26