CP5.241 Datasheet, PDF (24/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
24.6. SERIES OPERATION
Power supplies of the same type can be connected in series for higher
output voltages. It is possible to connect as many units in series as needed,
providing the sum of the output voltage does not exceed 150Vdc. Voltages
with a potential above 60Vdc are not SELV any more and can be dangerous.
Such voltages must be installed with a protection against touching.
Avoid return voltage (e.g. from a decelerating motor or battery) which is
applied to the output terminals.
Keep an installation clearance of 15mm (left / right) between two power
supplies and avoid installing the power supplies on top of each other. Do
not use power supplies in series in mounting orientations other than the
standard mounting orientation (input terminals on bottom of the unit).
Unit A
Input
+
-
Output
Unit B
Input
+
-
Output
+
Load
-
Pay attention that leakage current, EMI, inrush current, harmonics will increase when using multiple power supplies.
24.7. INDUCTIVE AND CAPACITIVE LOADS
The unit is designed to supply any kind of loads, including capacitive and inductive loads. If extreme large capacitors,
such as EDLCs (electric double layer capacitors or “UltraCaps”) with a capacitance > 0.4F are connected to the output,
the unit might charge the capacitor in the HiccupPLUS® mode (see chapter 6).
24.8. CHARGING OF BATTERIES
The power supply can be used to charge lead-acid or maintenance free batteries. Two 12V SLA or VRLA batteries are
needed in series connection.
Instructions for charging batteries:
a) Set output voltage (measured at no load and at the battery end of the cable) very precisely to the end-of-charge
voltage.
End-of-charge voltage
27.8V
27.5V
27.15V
26.8V
Battery temperature
10°C
20°C
30°C
40°C
b) Use a 10A circuit breaker (or blocking diode) between the power supply and the battery.
c) Ensure that the output current of the power supply is below the allowed charging current of the battery.
d) Ensure that the ambient temperature of the power supply stays below 40°C.
e) Use only matched batteries when putting 12V types in series.
f) The return current to the power supply (battery discharge current) is typ. 8mA when the power supply is switched
off (except in case a blocking diode is utilized).
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany