CP5.241 Datasheet, PDF (16/26 Pages) PULS GmbH – 24V, 5A, 120W, SINGLE PHASE INPUT
PRELIMINARY
CP-Series
CP5.241, CP5.241-C1,
CP5.241-S1, CP5.241-S2
24V, 5A, 120W, SINGLE PHASE INPUT
17. PROTECTION FEATURES
Output protection
Output over-voltage protection
Degree of protection
Penetration protection
Over-temperature protection
Input transient protection
Internal input fuse
Electronically protected against overload, no-load and short-circuits.
In case of a protection event, audible noise may occur.
Typ. 30.5Vdc
Max. 32Vdc
In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.
IP 20
According to EN/IEC 60529
Caution: For use in a controlled environment according to
CSA 22.2 No 107.1-01.
> 3.5mm
E.g. screws, small parts
Yes
Output shut-down with automatic restart.
Temperature sensors are installed on critical components
inside the unit and turn the unit off in safety critical
situations, which can happen e.g. when de-rating
requirements are not observed, ambient temperature is
too high, ventilation is obstructed or the de-rating
requirements are not followed. There is no correlation
between the operating temperature and turn-off
temperature since this is dependent on input voltage, load
and installation methods.
MOV
For protection values see chapter 15 (EMC).
(Metal Oxide Varistor)
Included
Not user replaceable slow-blow high-braking capacity fuse
18. SAFETY FEATURES
Input / output separation
Class of protection
Isolation resistance
PE resistance
Touch current (leakage current)
Double or reinforced insulation
SELV
According to IEC/EN 60950-1
PELV
According to IEC/EN 60204-1, EN 62477-1, IEC 60364-4-41
I
PE (Protective Earth) connection required
> 500MOhm
At delivered condition between input and output,
measured with 500Vdc
> 500MOhm
At delivered condition between input and PE, measured
with 500Vdc
> 500MOhm
At delivered condition between output and PE, measured
with 500Vdc
> 500MOhm
At delivered condition between output and DC-OK
contacts, measured with 500Vdc
< 0.1Ohm
Resistance between PE terminal and the housing in the
area of the DIN-rail mounting bracket.
T.b.d.
At 100Vac, 50Hz, TN-,TT-mains / IT-mains
T.b.d.
At 120Vac, 60Hz, TN-,TT-mains / IT-mains
T.b.d.
At 230Vac, 50Hz, TN-,TT-mains / IT-mains
T.b.d.
At 110Vac, 50Hz, TN-,TT-mains / IT-mains
T.b.d.
At 132Vac, 60Hz, TN-,TT-mains / IT-mains
T.b.d.
At 264Vac, 50Hz, TN-,TT-mains / IT-mains
Aug. 2017 / Rev. 0.1 DS-CP5.241-EN
All parameters are typical values specified at 24V, 5A output, 230Vac input, 25°C ambient and
after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
16/26