Appendix C: NFPA Standard-Specific Requirements Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Digital Alarm Communicator/Transmitter - Noti-Fire 911AC
Note: This application is not FM approved
Using the Noti-Fire 911AC DACT for connection to a Central Station Receiver or Protected Premises
Receiving Unit.
• AC Wiring for DACT/FACP must be connected to the same circuit.
• If the unit is not mounted in the control panel’s backbox all connections must be in conduit, less
than 20 ft. (609.6 cm) in length in the same room.
• For additional information refer to the Noti-Fire 911AC Instruction manual.
See Below for Terminal
Connections
To Central
Station
To AC Power
+
PS 1270
12Volt
–
7AH Battery
Control Panel
IN #1
IN #2
IN #3
IN #4
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–
TB4
TB3
4XZM Zone
Relay Module
JP1
TB1
GEN
ALM1
GEN
ALM2
SUPV 1
SUPR 2
J2
LATCH
DISABLE
STD DACT
OPT1
Jumper
TB3
Place jumper over pins as shown when employing
a DACT. This directs the control panel to transmit
all trouble conditions except AC LOSS.
Figure 24 DACT Connections
To Common
Terminal of Relay
46
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01