Setting Mode of Operation
2. Installation
Discharge Timer
Select the desired discharge timer setting by setting DIP Switches 3, 4 and 5 accordingly.
⢠For NFPA 13 and 15 applications timer must be set to âDisabledâ.
⢠For NFPA 16 applications timer may be set to â10 Minutesâ or â15 Minutesâ.
Disabled
10 Minutes
15 Minutes
Switch #3
OFF
ON
ON
Switch #4
OFF
ON
ON
Switch #5
OFF
OFF
ON
Note: Timer will always start at Zone 2 normal to alarm transition. Upon timeout, corresponding release circuits will
shut off.
Note: Zone 1 will always override timer shutoff (except for Mode #4 - Split Release).