English
Language : 

PDRP-1001 Datasheet, PDF (29/56 Pages) Systemsensor advanced ideas. – Deluge - Preaction Control Panel
Setting Mode of Operation
2. Installation
Discharge Timer
Select the desired discharge timer setting by setting DIP Switches 3, 4 and 5 accordingly.
• For NFPA 13 and 15 applications timer must be set to “Disabled”.
• For NFPA 16 applications timer may be set to “10 Minutes” or “15 Minutes”.
Disabled
10 Minutes
15 Minutes
Switch #3
OFF
ON
ON
Switch #4
OFF
ON
ON
Switch #5
OFF
OFF
ON
Note: Timer will always start at Zone 2 normal to alarm transition. Upon timeout, corresponding release circuits will
shut off.
Note: Zone 1 will always override timer shutoff (except for Mode #4 - Split Release).
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
29