PDRP-1001 Datasheet, PDF (27/56 Pages) Systemsensor advanced ideas. – Deluge - Preaction Control Panel
Optional Modules
2. Installation
LED Interface Module - 4XLM
Connect the terminals on TB1 of the LED Interface Module to the corresponding terminals of the RZA-
4X Remote Annunciator.
Make wiring connections with system power off.
Maximum wire impedance is 50 ohm per wiring connection.
The wiring of this module must follow the requirements as specified under "Power-limited Wiring
Requirements" on page 17.
+24V
Out #1
Out #2
Out #3
Out #4
Sysyem Trouble
Sound
Resound
J2
Connect to corresponding
terminals of the RZA-4X
Remote Annunciator.
SYSTEM TROUBLE
RE-SOUND
TONE
SILENCE
Single-gang
Box
FIRE ALARM ANNUNCIATOR
Front View
Side View
Figure 18 Connection of 4XLM to RZA-4X
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
27