PDRP-1001 Datasheet, PDF (28/56 Pages) Systemsensor advanced ideas. – Deluge - Preaction Control Panel
2. Installation
Setting Mode of Operation
Setting Mode of Operation
Select operating mode by setting the SW1 DIP switches as described below.
After any changes are made to the configuration of the switches, the panel must be reset.
For Canadian use, refer to "Sprinkler Supervisory Tracking" on page 34.
SW1
Basic Programming
Switch 1: Cross Zone
Switch 2: Dual Hazard
Not Used
Discharge Timer
Switch 3: Discharge Timer
Switch 4: Discharge Timer
Switch 5: Discharge Timer
Figure 19 DIP Switch Settings
Basic Program
Select the desired mode of operation and set DIP Switches 1 and 2 per the appropriate column.
Switch 1
Switch 2
Mode 1
Two Zone
Single Hazard
OFF
OFF
Mode 2
Cross Zone
Single Hazard
ON
OFF
Mode 3
Combined Release
Dual Hazard
OFF
ON
Mode 4
Split Release
Dual Hazard
ON
ON
Output 1 & 3 -
Activated by an
alarm on either IDC
1 or 2.
Output 2 -
Activated by a
waterflow alarm on
IDC 3.
Output 4 -
Activated by a
supervisory condition
on IDC 4.
Output 1 -
Activated by an
alarm on either IDC
1 or 2.
Output 2 -
Activated by a
waterflow alarm on
IDC 3.
Output 3 -
Activated by alarms
on both IDC 1 and 2.
Output 4 -
Activated by a
supervisory condition
on IDC 4.
Output 1 -
Activated by an
alarm on either IDC
1 or 2 or a waterflow
alarm on IDC 3.
Output 2 -
Activated by a
supervisory condition
on IDC 4.
Output 3 & 4 -
Activated by an
alarm on either IDC
1 or 2.
Output 1 -
Activated by an
alarm on either IDC
1 or 2 or a waterflow
alarm on IDC 3.
Output 2 -
Activated by a
supervisory condition
on IDC 4.
Output 3 -
Activated by an
alarm on IDC 1.
Output 4 -
Activated by an
alarm on IDC 2.
Note: Output 1 and 2 refer to Notification Appliance Circuits; Output 3 and 4 refer to Releasing Circuits.
28
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01