English
Language : 

PDRP-1001 Datasheet, PDF (31/56 Pages) Systemsensor advanced ideas. – Deluge - Preaction Control Panel
3. System Operation
System Status LEDs
Alarm, Trouble and Supervisory LEDs will flash on and off until the event(s) has been acknowledged
(TONE or ALARM SILENCE), at which point the LED will illuminate steadily.
System
Status
LEDs
AC POWER
SYSTEM
ALARM
RELEASE
SUPERVISORY
SYSTEM
TROUBLE
CIRCUIT
TROUBLE
ALARM
SILENCED
POWER
TROUBLE
ZONE 1
ZONE 2
WATERFLOW
SUPERVISORY
TONE ALARM ALARM SYSTEM
SILENCE SILENCE ACTIVATE RESET
BATT EARTH
MICRO
FAIL
Figure 21 System Status LEDs
AC Power - Green LED that illuminates steadily to indicate presence of AC power.
System Alarm - Red LED that flashes when an alarm occurs.
Release - Red LED that illuminates steadily when release occurs. After the Discharge Timer has expired,
the LED will flash.
Supervisory - Yellow LED that flashes upon activation of a supervisory device (such as tamper switch)
on IDC 4.
System Trouble - Yellow LED that flashes for any trouble condition, including those associated with
optional boards.
Circuit Trouble - Yellow LED that flashes for trouble conditions on output circuits (notification and
releasing).
Alarm Silenced - Yellow LED that illuminates steadily when the ALARM SILENCE switch has been
pushed after an alarm.
Power Trouble - Yellow LED that flashes for low or disconnected batteries and earth fault conditions.
The following LEDs are located below the main panel and are visible only when the panel door is open.
Battery Fail (BATT) - Yellow LED that illuminates steadily on motherboard when battery is low or not
detected.
Ground Fault (EARTH) - Yellow LED that illuminates steadily on motherboard during a ground fault
condition.
Micro Fail - Yellow LED that illuminates on motherboard when watchdog timer detects microprocessor
failure.
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
31