2. Installation
Optional Modules
Zone Relay Module - 4XZM
Note: The PAR-3 includes one (1) Zone Relay Module (4XZM).
Relay #1 through #4 on this module will activate with outputs #1 through #4.
For non-latching (silenceable) relay operation, cut the jumper “LATCH”. If this jumper is left intact, the
relays will latch upon activation. To disconnect relays entirely, slide the disable switch to the right.
Note: If any dry contacts are to be used as nonpower-limited circuits, write this on the Protected Premises Unit label,
located on the door of the control panel.
TB1
J2
LATCH
DISABLE
“Latch” Jumper
Disable Switch
Figure 16 Wiring the Zone Relay Module
The wiring of this module must follow the requirements specified under "Power-limited Wiring
Requirements" on page 17.
• If this module is used to drive both nonpower-limited and power-limited circuits, skip one set of
dry contacts to maintain the required separation between circuit types.
• If this module is used to drive both nonpower-limited and power-limited relays that are next to each
other, refer to the figure below which shows the one allowable arrangement.
Power-Limited
Circuit
No Connection
Nonpower-Limited
Circuit
Figure 17 Mixing Power-Limited and Nonpower-Limited Circuits
26
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01