Power-limited Wiring Requirements
2. Installation
Observe polarity when connecting the batteries. Connect the battery cable (p/n 75203 or 75202, depending
on terminal size of battery) to terminal J9 on the main circuit board using the plug-in connector provided.
Connect red wire to positive (+) terminal and black wire to negative (–) terminal on opposing batteries.
Do NOT connect battery interconnect wire at this time.
TB5
J2
AMP
J9
J3
Figure 5 Battery Installation and Connection
Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-
limited circuit wiring must remain at least 0.25 in (6.35 mm) away from any nonpower-limited circuit
wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must pass
through separate knockouts and/or conduits.
Power-limited Nonpower-limited
Circuits Circuits
Power-limited Circuits
AC Power
TB1
J1
TB5
J2
AMP
J9
J3
OUT#1
OUT#2
B+ A+ A– B– B+ A+ A– B–
OUT#3
B+ B–
OUT#4
B+ B–
ALARM
NO NC C
TB2 TB3
IN #1
IN #2
IN #3
IN #4
B+ A+ A– B– B+ A+ A– B– B+ A+ A– B– B+ A+ A– B–
TB4
JP1
GEN
ALM1
SUPV 1
TB1
GEN
SUPR 2
ALM2
AC POWER
S YST EM
ALARM
ALARM T EST
SUPERVISORY
S YST EM
TROUBLE
CIRCUIT
TROUBLE
ALARM
S IL EN CE D
POWER
TROUBLE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
TONE ALARM ALARM SYSTEM
SILENCE SILENCE ACTIVATE RESET
SW1
TJB4L
J5J1
J2
OPT1
TB1
J10
J7
J8
J2
OPT2
LATCH
DISABLE
Power-limited
Circuits
Nonpower-limited
Circuits
Figure 6 Power-limited Wiring Requirements
PDRP-1001 Instruction Manual PN 50734:D0 04/06/01
17