Appendix C: NFPA Standard-Specific Requirements
Minimum System Requirements
The control panel has been designed for use in commercial, industrial, and institutional applications and
meets the requirements for service under the National Fire Protection Association (NFPA) Standards
outlined in this appendix. The minimum system components required for compliance with the appropriate
NFPA standard are listed below.
• Fire Alarm Control Panel. Contains the main control board, cabinet (backbox and door), main
supply transformer and power supply.
• Batteries. Refer to "Appendix A: Secondary Power Calculations" on page 37
• Initiating Devices. Connected to one of the control panel's Initiating Device Circuits.
• Notification Appliances. Connected to one of the control panel's Notification Appliance Circuits.
• Releasing Devices. Connected to one of the control panel’s Releasing Circuits.
Additional Requirements
The following additional equipment is needed for compliance with the NFPA standards listed below. The
relay contacts of this control panel may be used to trip any dialer that is UL listed for Central Station/Remote
Station services. The illustrations in this appendix provide examples of possible system configurations.
Note: Applications which require the the NOTI-FIRE 911AC are not FM approved.
NFPA 72 - Signaling Systems for Central Station Service (Protected Premises Unit)
• NOTI-FIRE 911AC Digital Alarm Communicator/Transmitter (DACT) connected to a
compatible listed Central Station DACR or Protected Premises Receiving Unit. See "Digital Alarm
Communicator/Transmitter - Noti-Fire 911AC" on page 46 for installation instructions for this unit.
• 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central
Station DACR or Protected Premises Receiving Unit. See "Universal Digital Alarm Communicator
- 411UDAC" on page 47 for installation instructions for this unit.
NFPA 72 - Auxiliary Fire Alarm System
• 4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box.
See "Local Energy Municipal Box" on page 48 for installation instructions for this unit.
NFPA 72 - Remote Station Fire Alarm System
• Fire•Lite RS82-9 Remote Station Receiver connected to a 4XTM Transmitter Module. See
"Remote Station Receiver - RS82-9" on page 49 for installation instructions for this unit.
• NOTI-FIRE 911AC DACT connected to a compatible listed Central Station DACR. See "Digital
Alarm Communicator/Transmitter - Noti-Fire 911AC" on page 46 for installation instructions for
this unit
• 411UDAC Universal Digital Alarm Communicator connected to a compatible listed Central
Station DACR. See "Universal Digital Alarm Communicator - 411UDAC" on page 47 for
installation instructions for this unit.